Ascon tecnologic KX6 Series Engineering Manual Download Page 9

Ascon Tecnologic - KX6 - ENGINEERING MANUAL - Vr. 0.1

 PAG. 9

Alarm ACK

Alarm ACK

AL1

PV

time

off

off

Ab1 = +4

Ab1 = +0

off

off

off

ON

ON

ON

A “relative alarm not active at set point change” is 
an alarm that masks the alarm condition after a 
set point change until process variable reaches the 
alarm threshold ±hysteresis.

Sp2

Sp1

PV

time

Ab1 = +8

Ab1 = +0

ON

off

off

AL1

off

off

off

AL1

ON

ON

ON

ON

4. 

The instrument does not store in EEPROM the 
alarm status.  For this reason, the alarm status 
will be lost if a power down occurs.

[21] AL1L  - For High and low alarms, it is the low 

limit of the AL1 threshold 

 

- For band alarm, it is low alarm threshold

Available: 

When [19] AL1t is different from 

nonE

 or 

[19] AL1t is different from 

SE.br

.

range: 

From -1999 to [22] AL1H engineering units.

[22] AL1H - For High and low alarms, it is the high 

limit of the AL1 threshold

 

- For band alarm, it is the high alarm 

threshold

Available: 

When [19] AL1t is different from 

nonE

 or 

[19] AL1t is different from 

SE.br

.

range: 

 From [21] AL1L to 9999 engineering units.

[23] AL1- Alarm 1 threshold

Available: 

When:

[19] AL1t = LoAb - Absolute low alarm;

[19] AL1t = HiAb - Absolute high alarm;

[19] AL1t = LodE - Deviation low alarm (relative);
[19] AL1t = LidE - Deviation high alarm (relative).

range: 

From [21] AL1L to [22] AL1H engineering units.

[24] HAL1 - Alarm 1 hysteresis

Available: 

When [19] AL1t is different from 

nonE

 or 

[19] AL1t is different from 

SE.br

.

range: 

1... 9999 engineering units.

notes: 1. 

The hysteresis value is the difference between 
the Alarm threshold value and the point the Alarm 
automatically resets.

2. 

When the alarm threshold plus or minus the 
hysteresis is out of input range, the instrument will 
not be able to reset the alarm.

example:

 Input range 0... 1000 (mBar).

 

Set point equal to 900 (mBar);

 

Deviation low alarm equal to 50 (mBar);

 

Hysteresis equal to 160 (mBar) the theoretical reset point is 

900 - 50 + 160 = 1010 (mBar) but this value is out of range. 
The reset can be made only by turning the instrument 
OFF, removing the condition that generate the alarm and 
then turn the instrument ON again.

 

All band alarms use the same hysteresis value for both 
thresholds;

 

When the hysteresis of a band alarm is bigger than the 
programmed band, the instrument will not be able to reset 
the alarm.

example:

 Input range 0... 500 (°C).

 

Set point equal to 250 (°C);

 

Relative band alarm;

 

Low threshold equal to 10 (°C);

 

High threshold equal to 10 (°C);

 

Hysteresis equal to 25 (°C).

[25] AL1d - Alarm 1 delay

Available: 

When [19] AL1t is different from 

nonE

.

Range:  • 

0 (OFF);

• 

1... 9999 seconds.

note: 

The alarm goes ON only when the alarm condition 
persists for a time longer than [25] AL1d time but the 
reset is immediate.

[26] AL1o  - Alarm 1 enabling during Stand-by mode 

and out of range indications

Available: 

When [19] AL1t is different from 

nonE

.

range: 0

 Never;

1

  During stand by;

2

  During overrange and underrange;

3

  During overrange, underrange and stand-by.

]

Al2 group - Alarm 2 parameters

[27] AL2t - Alarm 2 type

Available: 

Aways.

range: 

nonE = Alarm not used;
LoAb =  Absolute low alarm;

HiAb =  Absolute high alarm;
LHAo =  Absolute band alarm with alarm indication 

out of the band;

LHAi =  Absolute band alarm with alarm indication 

inside the band;

SE.br =  Sensor break;
LodE =  Deviation low alarm (relative);

HidE =  Deviation high alarm (relative);
LHdo =  Relative band alarm with alarm indication 

out of the band;

LHdi =  Relative band alarm with alarm indication 

inside the band.

note: 

The relative alarm are “relative” to the current set point 
(this may be different from the Target set point if you are 
using the ramp to set point function).

[28] Ab2 - Alarm 2 function

Available: 

When [27] AL2t is different from 

nonE

.

range: 

0... 15 with the following rules:

+1

  Not active at power up;

+2

  Latched alarm (manual reset);

+4

  Acknowledgeable alarm;

+8

  Relative alarm not active at set point change.

example:

 Setting Ad2 equal to 5 (1+4) the alarm 2 will be 

“not active at power up” and “Acknowledgeable”.

note: 

For other details see [20] Ab1 parameter.

Summary of Contents for KX6 Series

Page 1: ...r permanent installation for indoor use only in an electrical panel which encloses the rear housing exposed terminals and wiring on the back Select a mounting location having the following characteris...

Page 2: ...0 mA input wiring for passive transmitter using an external power supply _ _ 1 2 0 4 20 mA Passive transmitter _ External PWS Input impedance 50W 0 4 20 mA input wiring for active transmitter 0 4 20 m...

Page 3: ...4 NO 9 C NO Alarm 1 OP3 Alarm 2 OP4 Load AC 8 10 Load Contact rating 2 A 250 V cosj 1 1 A 250 V cosj 0 4 Operation 1 x 105 2 4 Serial Interface RS 485 D D GND 17 18 16 D D GND D D GND D D GND Interfac...

Page 4: ...0 023 in Weight 160 g max Power supply 100 240 VAC 15 10 of the nominal value Power consumption 5 VA max Insulation voltage 2300 V rms according to EN 61010 1 Display updating time 500 ms Sampling tim...

Page 5: ...s to take advantage of all instrument features The instrument have one complete parameter set indicated as Configuration parameter set or Configuration parameters The access to the configuration param...

Page 6: ...buttons set the value 581 3 Push button 4 The instrument turns ON all the LEDs for a few seconds then returns to the Standard display mode Notes 1 If the instrument does NOT TURN ON ALL the LEDs for...

Page 7: ...out 2 output while the values greater than zero activate the Open valve out 1 output 4 When ON OFF control is programmed and an out of range is detected the instrument performs the safety output valu...

Page 8: ...tion low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the band LHdi Relative band alarm with alarm indication inside the band Notes 1 The rel...

Page 9: ...1010 mBar but this value is out of range The reset can be made only by turning the instrument OFF removing the condition that generate the alarm and then turn the instrument ON again All band alarms u...

Page 10: ...to 0 the tempera ture must go down if not the SSR is in short circuit the valve is jammed and so on So the LBA should be generated LBA function is automatically enabled when the PID requires the maxi...

Page 11: ...7 EvoTune with manual start 8 EvoTune with automatic restart at all set point change 41 tunE Manual start of the auto tune Available Always Range oFF The instrument is not performing the auto tune on...

Page 12: ...start time Available When 39 cont PID or 39 cont 3Pt and 58 Pot Pot c Range oFF Function not used 0 01 7 59 hh mm inF Soft start always active Note The time calculation starts at Power ON and is inte...

Page 13: ...Note For other details see 61 SPLL parameter 63 SP Set Point 1 Available Always Range From 61 SPLL to 62 SPHL engineering units 64 SP 2 Set Point 2 Available When 60 nSP 2 Range From 61 SPLL to 62 SP...

Page 14: ...The first press puts the in strument in stand by mode while a second one puts the instrument in Auto mode SP1 2 SP SP2 selection Notes 1 When SP1 2 is used every press of the button longer than 1 sec...

Page 15: ...ence between AL P and AH P is equal to 10 Engineering Units 87 AL o Adjust Low Offset Available Always Range 300 300 engineering units 88 AH P Adjust High Point Available Always Range From AL P 10 to...

Page 16: ...L2 Pb A 7 Pb ti A 8 ti td A 9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds The upper display will show PASS while the middle display shows 0 2 By and buttons se...

Page 17: ...assword Notes 1 The factory default password for configuration parameters is 20 2 Operator and assistace level of Parameter modification are protected by a time out If no button is pressed for more th...

Page 18: ...always on display and no button is pressed for more than the programmed time out the display goes OFF and only 4 segments of the less significant digit are turned ON in sequence in order to show that...

Page 19: ...lectrical equipment for measurement control and laboratory use for this reason it could not be used as a safety equipment Whenever a failure or a malfunction of the control device may cause dangerous...

Page 20: ...to use it ti configure other instruments To transfer a complete instrument configuration to a PC or from a PC to an instrument To transfer a complete instrument configuration from a PC to an instrumen...

Page 21: ...Digital Input 2 function oFF 11 di A Digital Inputs Action DI2 only if configured 0 DI1 direct action DI2 direct action 1 DI1 reverse action DI2 direct action 2 DI1 direct action DI2 reverse action 3...

Page 22: ...n stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in out of range condition 0 AL2 group no Param Description Dec Point Values Default 27 AL2t Alarm 2 t...

Page 23: ...ower up and after a set point change 5 Evo tune with automatic restart at every power up 6 Evo tune with automatic start the first power up only 7 Evo tune with manual start 8 Evo tune with automatic...

Page 24: ...nction tunE Auto tune self tune enabling A single press longer than 1 se cond starts the auto tune oPLo Manual mode The first pressure puts the instrument in manual mode oPLo while a second one puts t...

Page 25: ...ted Master nonE Retransmission not used the instrument is a slave rSP The instrument becomes a Master and retransmits the operative set point PErc The instrument become a Master and it retransmits the...

Page 26: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 26...

Page 27: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 27...

Page 28: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 28...

Reviews: