Ascon tecnologic KX6 Series Engineering Manual Download Page 10

Ascon Tecnologic - KX 6 - ENGINEERING MANUAL - Vr. 0.1

 PAG. 10

[29] AL2L  - For High and low alarms, it is the low 

limit of the AL2 threshold

 - 

For band alarm, it is low alarm threshold

Available: 

When [27] AL2t is different from 

nonE

 or 

[27] AL2t is different from 

SE.br

.

range: 

-1999 to [30] AL2H engineering units.

[30] AL2H - For High and low alarms, it is the high 

limit of the AL2 threshold

 - 

For band alarm, it is high alarm threshold

Available: 

When [27] AL2t is different from 

nonE

 or 

[27] AL2t is different from 

SE.br

.

range: 

From [29] AL2L to 9999 engineering units.

[31] AL2 - Alarm 2 threshold

Available: 

When:

[27] AL2t = LoAb Absolute low alarm;

[27] AL2t = HiAb Absolute high alarm;

[27] AL2t = LodE Deviation low alarm (relative);
[27] AL2t = LidE Deviation high alarm (relative).

range: 

From [29] AL2L to [30] AL2H  engineering units.

[32] HAL2 - Alarm 2 hysteresis

Available: 

When [27] AL2t is different to 

nonE

 or  

[27] AL2t is different from 

SE.br

.

range: 

 1... 9999 engineering units.

note: 

For more details see [24] HAL1 parameter.

[33] AL2d - Alarm 2 delay

Available: 

When [27] AL2t different from 

nonE

.

Range:  • 

0 (OFF);

• 

1... 9999 seconds.

note: 

The alarm goes ON only when the alarm condition 
persists for a time longer than [33] AL2d time but the 
reset is immediate.

[34] AL2o - Alarm 2 enabling during Stand-by mode 

and out of range indications

Available: 

When [27] AL2t different from 

nonE

.

range: 0

 Never;

1

  During stand by;

2

  During overrange and underrange;

3

  During overrange, underrange and stand-by.

]

 lbA group - loop break alarm

General note about LBA alarm

The LBA operates as follows: applying the 100% of the power 
output to a process, the process variable should change (with a 
delay due to the process inertia) in a known direction (increases 
for a heating action or decreases for a cooling action).  If this 
does not happen, the LBA alarm is generated.

example:

 Applying the 100% of the power output to a furnace, 

the temperature must go up unless one of the component in 
the loop is faulty (heater, sensor, power supply, fuse, etc...).
The same is applied to the minimum power.  In our example, 
when the furnace power is turned down to 0%, the tempera-
ture must go down, if not the SSR is in short circuit, the valve 
is jammed, and so on.  So the LBA should be generated.
LBA function is automatically enabled when the PID requires 
the maximum or the minimum power.
When the process response is slower than the programmed 
limit the instrument generates an alarm.

notes: 1. 

When the instrument is in manual mode, the LBA 
function is disabled.

2. 

When LBA alarm is ON the instrument continues 

to perform the standard control.  If the process 
response comes back into the programmed limit, 
the instrument automatically resets the LBA alarm.

[35] LbAt - LBA time

Available: 

Always.

Range:  • 

oFF = LBA not used;

• 

1... 9999 seconds.

[36] LbSt  - Delta measure used by LBA during Soft 

start

Available: 

When [35] LbAt is different from 

oFF

.

Range:  • 

oFF = loop break alarm is inhibit during soft start;

• 

1... 9999 engineering units.

[37] LbAS - Delta measure used by loop break alarm 

(loop break alarm step)

Available: 

When [35] LbAt is different from 

oFF

.

range: 

1... 9999 engineering units.

[38] LbcA - Condition for LBA enabling

Available: 

When [35] LbAt is different from 

oFF

.

range: up

 =  

Enabled when PID requires the maximum 
power only;

dn

 =  

Enabled when PID requires the minimum 
power only;

both

 =   Enabled in both condition (when PID re-

quires the maximum or the minimum power).

LBA application example: 
 

LbAt (LBA time) = 120 seconds (2 minutes);

 

LbAS (delta LBA) = 5°C.

The machine has been designed in order to reach 200°C in 
20 minutes (20°C/min).
When the PID demands 100% power, the instrument starts 
the time count.
During time count if the measured value increases more 
than 5°C, the instrument restarts the time count.  Otherwise 
if the measured value does not reach the programmed delta 
(5°C in 2 minutes) the instrument will generate the alarm.

]

reg group - Control parameters

[39] cont - Control type

Available: 

When at least one output is programmed as con-

trol output (H.rEG or C.rEG).

Range:  • 

When two control actions (heat & cool) are pro-
grammed:

pid

 = 

PID (heat and cool);

nr

 =  

Heat/Cool ON/OFF control with neutral zone;

HSEt
HSEt

SP

PV

time

OUTH.rEG

(heating)
OUTc.rEG

(cooling)

off

ON

ON

off

off

ON

• 

When one control action (heat or cool) is pro-
grammed:

pid

 = 

PID (heat or cool);

on.FA

 = ON/OFF asymmetric hysteresis;

on.Fs

 = ON/OFF symmetric hysteresis;

3pt

 = 

Servomotor control.

Summary of Contents for KX6 Series

Page 1: ...r permanent installation for indoor use only in an electrical panel which encloses the rear housing exposed terminals and wiring on the back Select a mounting location having the following characteris...

Page 2: ...0 mA input wiring for passive transmitter using an external power supply _ _ 1 2 0 4 20 mA Passive transmitter _ External PWS Input impedance 50W 0 4 20 mA input wiring for active transmitter 0 4 20 m...

Page 3: ...4 NO 9 C NO Alarm 1 OP3 Alarm 2 OP4 Load AC 8 10 Load Contact rating 2 A 250 V cosj 1 1 A 250 V cosj 0 4 Operation 1 x 105 2 4 Serial Interface RS 485 D D GND 17 18 16 D D GND D D GND D D GND Interfac...

Page 4: ...0 023 in Weight 160 g max Power supply 100 240 VAC 15 10 of the nominal value Power consumption 5 VA max Insulation voltage 2300 V rms according to EN 61010 1 Display updating time 500 ms Sampling tim...

Page 5: ...s to take advantage of all instrument features The instrument have one complete parameter set indicated as Configuration parameter set or Configuration parameters The access to the configuration param...

Page 6: ...buttons set the value 581 3 Push button 4 The instrument turns ON all the LEDs for a few seconds then returns to the Standard display mode Notes 1 If the instrument does NOT TURN ON ALL the LEDs for...

Page 7: ...out 2 output while the values greater than zero activate the Open valve out 1 output 4 When ON OFF control is programmed and an out of range is detected the instrument performs the safety output valu...

Page 8: ...tion low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the band LHdi Relative band alarm with alarm indication inside the band Notes 1 The rel...

Page 9: ...1010 mBar but this value is out of range The reset can be made only by turning the instrument OFF removing the condition that generate the alarm and then turn the instrument ON again All band alarms u...

Page 10: ...to 0 the tempera ture must go down if not the SSR is in short circuit the valve is jammed and so on So the LBA should be generated LBA function is automatically enabled when the PID requires the maxi...

Page 11: ...7 EvoTune with manual start 8 EvoTune with automatic restart at all set point change 41 tunE Manual start of the auto tune Available Always Range oFF The instrument is not performing the auto tune on...

Page 12: ...start time Available When 39 cont PID or 39 cont 3Pt and 58 Pot Pot c Range oFF Function not used 0 01 7 59 hh mm inF Soft start always active Note The time calculation starts at Power ON and is inte...

Page 13: ...Note For other details see 61 SPLL parameter 63 SP Set Point 1 Available Always Range From 61 SPLL to 62 SPHL engineering units 64 SP 2 Set Point 2 Available When 60 nSP 2 Range From 61 SPLL to 62 SP...

Page 14: ...The first press puts the in strument in stand by mode while a second one puts the instrument in Auto mode SP1 2 SP SP2 selection Notes 1 When SP1 2 is used every press of the button longer than 1 sec...

Page 15: ...ence between AL P and AH P is equal to 10 Engineering Units 87 AL o Adjust Low Offset Available Always Range 300 300 engineering units 88 AH P Adjust High Point Available Always Range From AL P 10 to...

Page 16: ...L2 Pb A 7 Pb ti A 8 ti td A 9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds The upper display will show PASS while the middle display shows 0 2 By and buttons se...

Page 17: ...assword Notes 1 The factory default password for configuration parameters is 20 2 Operator and assistace level of Parameter modification are protected by a time out If no button is pressed for more th...

Page 18: ...always on display and no button is pressed for more than the programmed time out the display goes OFF and only 4 segments of the less significant digit are turned ON in sequence in order to show that...

Page 19: ...lectrical equipment for measurement control and laboratory use for this reason it could not be used as a safety equipment Whenever a failure or a malfunction of the control device may cause dangerous...

Page 20: ...to use it ti configure other instruments To transfer a complete instrument configuration to a PC or from a PC to an instrument To transfer a complete instrument configuration from a PC to an instrumen...

Page 21: ...Digital Input 2 function oFF 11 di A Digital Inputs Action DI2 only if configured 0 DI1 direct action DI2 direct action 1 DI1 reverse action DI2 direct action 2 DI1 direct action DI2 reverse action 3...

Page 22: ...n stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in out of range condition 0 AL2 group no Param Description Dec Point Values Default 27 AL2t Alarm 2 t...

Page 23: ...ower up and after a set point change 5 Evo tune with automatic restart at every power up 6 Evo tune with automatic start the first power up only 7 Evo tune with manual start 8 Evo tune with automatic...

Page 24: ...nction tunE Auto tune self tune enabling A single press longer than 1 se cond starts the auto tune oPLo Manual mode The first pressure puts the instrument in manual mode oPLo while a second one puts t...

Page 25: ...ted Master nonE Retransmission not used the instrument is a slave rSP The instrument becomes a Master and retransmits the operative set point PErc The instrument become a Master and it retransmits the...

Page 26: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 26...

Page 27: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 27...

Page 28: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 28...

Reviews: