6.  ConFigurAtion proCedure

6.1  introduCtion

When the instrument is powered, it starts immediately to work 
according to the parameters values loaded in its memory.
The instrument behaviour and its performance are controlled 
by the value of the stored parameters.
At the first start up the instrument will use a “default” 
parameter set (factory parameter set); this set is a generic 
one (e.g. a TC J input is programmed).

wArning!  before connecting the output actuators

,  

we recommend to configure the parameters to 
suit your application (e.g.: input type, Control 
strategy, alarms, etc.).

wArning! 

Do not change the 

[5] unit (engineering unit)

 

value during process control as the set point 
inserted by the user (thresholds, limits etc.) are 
not automatically rescaled by the instrument.

To change these parameters you need to enter the 
“Configuration mode”.

6.2  instrument behAviour At 

power on

At power ON the instrument can start in one of the following 
mode depending on its configuration:

Auto mode

.

 

The upper display will show the measured value;

 

The middle display will show the Set point value;

 

The lower display will show the valve position (measured 
or theoretical according to the control strategy selected).

 

The instrument is performing the standard PID control with 
servo-motor drive output.

Manual mode

 (oPLo).

 

The upper display shows the measured value;

 

The middle display shows the power output [preceded by 

H

 

(for heating) or 

C

 (for cooling)].  The MAN LED is lit;

 

The lower display will show the valve position (measured 
or theoretical according to the selected control).

 

The instrument does not perform Automatic control;

 

The control output can be manually modified by 

 and 

 buttons.

Stand by mode

 (St.bY).

 

The upper display will show the measured value;

 

The middle display will show alternately the set point value 
and the message 

St.bY

 or 

od

;

 

The lower display will show the valve position (measured 
or theoretical according to the control strategy selected).

 

The instrument perform no control at all  
(Out 2 [close] is always ON);

 

The instrument is working as an indicator.

We define all the above described conditions as  

standard display

”.

6.3  entering in the  

“ConFigurAtion modes”

The configuration mode allows to take advantage of all 
instrument features.
The instrument have one complete parameter set indicated as 

Configuration parameter set

” (or “

Configuration parameters

”)

The access to the configuration parameters is protected by a 
password.

note: 

The instrument shows only those parameters that are 
consistent with the hardware and in accordance with the 
value assigned to the previous parameters (e.g.: if you 
set an Alarm as “not used”, the instrument masks all the 
remaining  parameters related to this Alarm).

6.3.1  Complete configuration procedure

The configuration parameters are collected in various 
groups.  Every group defines all parameters related with a 
specific function (e.g.: control, alarms, output functions).

1. 

Push the 

 button for more than 5 seconds.  The upper 

display will show 

PASS

 while the middle display shows 

0

.

2. 

Using 

 and 

 buttons set the programmed password.

notes: 1. 

The factory default password for configuration 
parameters is equal to 

30

.

2. 

During parameter modification the instrument 
continue to perform the control. 
In certain conditions, when a configuration 
change can produce a heavy bump to the 
process, it is advisable to temporarily stop the 
control during programming procedure. 
When it is desired to stop the control during 
progrmming procedure, use a password equal to 
2000 + the programmed value (2000 + 30 = 2030). 
The control restarts automatically when the 
configuration procedure will be manually closed.

3. 

Push the 

 button. 

If the password is correct the display shows the acronym of 
the first parameter group preceded by the symbol: 

]

In other words the upper display shows: 

]inp

  

(group of the 

input parameters

).

The instrument is in configuration mode.

4. 

If the password is not correct, the instrument returns to 
the Standard Display.

6.4  leAving the “ConFigurAtion mode”

Pushing the 

 button for more than 5 seconds, the 

instrument returns to the “Standard display”.

6.5  KeyboArd FunCtions during 

pArAmeter ChAnging

  A short press allows to exit from the current parameter 

group and select a new parameter group.

 

A long press allows you to close the configuration 
parameter procedure (the instrument will come back 
to the “standard display”).

  When the upper display is showing a group and the 

middle display is blank, this key allows to enter in the 
selected group.

 

When the upper display is showing a parameter and 
the middle display is showing its value, this key allows 
to store the selected value for the current parameter 

Summary of Contents for KX6 Series

Page 1: ...r permanent installation for indoor use only in an electrical panel which encloses the rear housing exposed terminals and wiring on the back Select a mounting location having the following characteris...

Page 2: ...0 mA input wiring for passive transmitter using an external power supply _ _ 1 2 0 4 20 mA Passive transmitter _ External PWS Input impedance 50W 0 4 20 mA input wiring for active transmitter 0 4 20 m...

Page 3: ...4 NO 9 C NO Alarm 1 OP3 Alarm 2 OP4 Load AC 8 10 Load Contact rating 2 A 250 V cosj 1 1 A 250 V cosj 0 4 Operation 1 x 105 2 4 Serial Interface RS 485 D D GND 17 18 16 D D GND D D GND D D GND Interfac...

Page 4: ...0 023 in Weight 160 g max Power supply 100 240 VAC 15 10 of the nominal value Power consumption 5 VA max Insulation voltage 2300 V rms according to EN 61010 1 Display updating time 500 ms Sampling tim...

Page 5: ...s to take advantage of all instrument features The instrument have one complete parameter set indicated as Configuration parameter set or Configuration parameters The access to the configuration param...

Page 6: ...buttons set the value 581 3 Push button 4 The instrument turns ON all the LEDs for a few seconds then returns to the Standard display mode Notes 1 If the instrument does NOT TURN ON ALL the LEDs for...

Page 7: ...out 2 output while the values greater than zero activate the Open valve out 1 output 4 When ON OFF control is programmed and an out of range is detected the instrument performs the safety output valu...

Page 8: ...tion low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the band LHdi Relative band alarm with alarm indication inside the band Notes 1 The rel...

Page 9: ...1010 mBar but this value is out of range The reset can be made only by turning the instrument OFF removing the condition that generate the alarm and then turn the instrument ON again All band alarms u...

Page 10: ...to 0 the tempera ture must go down if not the SSR is in short circuit the valve is jammed and so on So the LBA should be generated LBA function is automatically enabled when the PID requires the maxi...

Page 11: ...7 EvoTune with manual start 8 EvoTune with automatic restart at all set point change 41 tunE Manual start of the auto tune Available Always Range oFF The instrument is not performing the auto tune on...

Page 12: ...start time Available When 39 cont PID or 39 cont 3Pt and 58 Pot Pot c Range oFF Function not used 0 01 7 59 hh mm inF Soft start always active Note The time calculation starts at Power ON and is inte...

Page 13: ...Note For other details see 61 SPLL parameter 63 SP Set Point 1 Available Always Range From 61 SPLL to 62 SPHL engineering units 64 SP 2 Set Point 2 Available When 60 nSP 2 Range From 61 SPLL to 62 SP...

Page 14: ...The first press puts the in strument in stand by mode while a second one puts the instrument in Auto mode SP1 2 SP SP2 selection Notes 1 When SP1 2 is used every press of the button longer than 1 sec...

Page 15: ...ence between AL P and AH P is equal to 10 Engineering Units 87 AL o Adjust Low Offset Available Always Range 300 300 engineering units 88 AH P Adjust High Point Available Always Range From AL P 10 to...

Page 16: ...L2 Pb A 7 Pb ti A 8 ti td A 9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds The upper display will show PASS while the middle display shows 0 2 By and buttons se...

Page 17: ...assword Notes 1 The factory default password for configuration parameters is 20 2 Operator and assistace level of Parameter modification are protected by a time out If no button is pressed for more th...

Page 18: ...always on display and no button is pressed for more than the programmed time out the display goes OFF and only 4 segments of the less significant digit are turned ON in sequence in order to show that...

Page 19: ...lectrical equipment for measurement control and laboratory use for this reason it could not be used as a safety equipment Whenever a failure or a malfunction of the control device may cause dangerous...

Page 20: ...to use it ti configure other instruments To transfer a complete instrument configuration to a PC or from a PC to an instrument To transfer a complete instrument configuration from a PC to an instrumen...

Page 21: ...Digital Input 2 function oFF 11 di A Digital Inputs Action DI2 only if configured 0 DI1 direct action DI2 direct action 1 DI1 reverse action DI2 direct action 2 DI1 direct action DI2 reverse action 3...

Page 22: ...n stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in out of range condition 0 AL2 group no Param Description Dec Point Values Default 27 AL2t Alarm 2 t...

Page 23: ...ower up and after a set point change 5 Evo tune with automatic restart at every power up 6 Evo tune with automatic start the first power up only 7 Evo tune with manual start 8 Evo tune with automatic...

Page 24: ...nction tunE Auto tune self tune enabling A single press longer than 1 se cond starts the auto tune oPLo Manual mode The first pressure puts the instrument in manual mode oPLo while a second one puts t...

Page 25: ...ted Master nonE Retransmission not used the instrument is a slave rSP The instrument becomes a Master and retransmits the operative set point PErc The instrument become a Master and it retransmits the...

Page 26: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 26...

Page 27: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 27...

Page 28: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 28...

Reviews: