Ascon Tecnologic - KX6 Series - ENGINEERING MANUAL - Vr. 0.0
PAG. 4
3. pAnel desCription
KX6
Process Value
(in eng. units)
Autotune
in progress
(flashing)
Programmable
display
(usually shows
the Set Point)
Output
LEDs
Manual
mode
Alarm
active
Eng. Unit
(°C/°F)
Potentio-
meter (*)
Digital
inputs ON
Valve
Open/Close
Valve position
(measured or
theoretical)
*
Lit when the instrument is using the potentiometer;
flashes when a potentiomter malfunction is detected.
4. teChniCAl ChArACteristiCs
4.1 teChniCAl speCiFiCAtion
Case:
Plastic, self-extinguishing degree: V-0 according to UL 94;
Front protection:
IP65 (when the optional panel gasket is
mounted) for indoor locations according to EN 60070-1;
terminals protection:
IP20 according to EN 60070-1;
installation:
Panel mounting;
terminal block:
24 M3 screw terminals for cables of
0.25... 2.5 mm
2
(AWG22... AWG14) with connection diagram;
dimensions:
48 x 96 depth 89.15 mm (1.77 x 3.78 x 3.51 in.);
panel cutout:
45
(+0.6)
x 89
(+0.6)
mm [1.78
(+0.023)
x 3.5
(+0.023)
in.];
weight:
160 g max..
power supply:
100... 240 VAC (-15... +10% of the nominal
value);
power consumption:
5 VA max.;
insulation voltage:
2300 V rms according to EN 61010-1;
display updating time:
500 ms;
sampling time:
130 ms;
resolution:
30000 counts;
total Accuracy:
±0.5% F.S.V. ±1 digit @ 25°C of room
temperature;
Electromagnetic compatibility and safety requirements
Compliance:
Directive EMC 2004/108/CE (EN 61326-1),
Directive LV 2006/95/CE (EN 61010-1);
installation category:
II;
pollution category:
2;
temperature drift:
It is part of the global accuracy;
operating temperature:
0... 50°C (32... 122°F);
storage temperature:
-30... +70°C (-22... +158°F);
humidity:
20... 85% RH, not condensing.
5. how to order
Power supply
H
= 100... 240 VAC
Analogue input + digital input DI1
(standard)
B
= J, K, R, S, T, mA
Output 3
R
= Relay SPST 2 A (resistive load)
Output 4
R
= Relay SPST 2 A (resistive load)
Options
(the TTL Modbus port is always present)
-
= Not available
C
= Potentiometer input + Digital Input 2 + RS 485 Modbus
P
= Potentiometer input + Digital Input 2
S
= RS 485 Modbus
Model
KX6
- = Valve Controller
Output 1 + Output 2
I-
= Output 1: 0/4... 20 mA, 0/2... 10 V; Output 2: Not available
MM
= Output 1 + Output 2: Relays for servomotor SPST 2 A
KX6- H B
R R