Ascon tecnologic KX6 Series Engineering Manual Download Page 6

Ascon Tecnologic - KX 6 - ENGINEERING MANUAL - Vr. 0.1

 PAG. 6

and access the next parameter within the same group.

  Allows to increase the value of the selected parameter.
  Allows to decrease the value of the selected parameter.
 + 

  These two keys allow to return to the previous 

group.  Proceed as follows: 

 

Push the 

 button, then maintaining the pressure 

push the 

 button; release both the buttons.

note: 

The group selection is cyclic as well as the selection 
of the parameters in a group.

6.6  FACtory reset - deFAult 

pArAmeters loAding proCedure

It is possible to restore the factory configuration when 
required,  For example to reset all the parameters after 
another use or after a wrongly set configuration.
This action allows to set the instrument in a defined condition 
using the default data (typically the same values loaded in the 
instrument during it’s production).
To load the factory default parameter set, proceed as follows:

1. 

Press the 

 button for more than 5 seconds.  The upper 

display will show 

PASS

 while the middle display shows 

0

;

2. 

Using 

 and 

 buttons set the value 

-481

;

3. 

Push 

 button;

4. 

The instrument will turn OFF all LEDs for a few seconds, 
then the upper display will show 

dFLt

 (default) and then 

all LEDs are turned ON for 2 seconds.  At this point the 
instrument restarts as for a new power ON.

The procedure is complete.

note: 

The complete list of the default parameters is available 
in Appendix A.

6.7  oem deFAult

In addition to the “Factory default” these instruments allow 
the OEM to store his own default parameter set.  In this way 
if an end-user tampers the parameter values, the OEM’s 
after sales support has a fast and easy way to reset the 
machine and return to the proprietary parameter set.

6.7.1  storing the oem’s default parameter set

Once the OEM has configured his own paratameter set and is 
returned to the “Standard display”, in order store these values 
as a “Proprietary default” the OEM must proceed as follows:

1. 

Press the 

 button for more than 5 seconds.  The upper 

display will show 

PASS

 while the middle display shows 

0

;

2. 

Using 

 and 

 buttons set the value 

-682

;

3. 

Push 

 button;

4. 

The instrument shows 

LoAd

 on the upper display in order 

to highlight that the memorization has been made, then 
returns to the “Standard display” mode.

6.7.2  loading the oem default parameter set

1. 

Press the 

 button for more than 5 seconds.  The upper 

display will show 

PASS

 while the middle display shows 

0

;

2. 

Using 

 and 

 buttons set the value 

-581

;

3. 

Push 

 button;

4. 

The instrument turns ON all the LEDs for a few seconds, 
then returns to the “Standard display” mode.

notes: 1. 

If the instrument does NOT TURN ON ALL the 
LEDs for at least 2 seconds means that the 

password was incorrect and the EOM parameter 
set has NOT been loaded.

2. 

Using the serial link it is always possible to send to 

the address 13H the corretct password in order to 

obtain the desired action (

-481

 for the Factory set, 

-581

 for OEM set or 

-682

 to store the OEM set).

6.8  ConFiguring All pArAmeters

The following pages describe the complete parameter set.

However, the instrument shows only the applicable parameters, 

according to its hardware options and the specific instrument 
configuration (i.e. setting 

AL1t

 [Alarm 1 type] to 

nonE

 [not 

used], all the parameters related to alarm 1 will be skipped).

]

inp group - main input configuration

[1] SEnS - Input type

Available: 

Always.

range:  J

 = 

TC J 

(0... 1000°C/32... 1832°F);

crAl

 = TC K 

(0... 1370°C/32... 2498°F);

s

 = 

TC S 

(0... 1760°C/32... 3200°F);

r

 = 

TC R 

(0... 1760°C/32... 3200°F);

t

 = 

TC T 

(0... 400°C/32... 752°F);

0.20

 =  0... 20 mA linear;

4.20

 =  4... 20 mA linear.

notes: 1. 

When a TC input is selected and a decimal figure 
is programmed (see the next parameter) the max. 
displayed value becomes 999.9°C or 999.9°F.

2. 

All changes to 

SEnS

 parameter setting, force 

[2] dP = 0.  This fact changes all parameters 
related to dP (Set points, Proportional band, etc.).

[2] dP - Decimal point position

Available: 

Always.

Range:  • 

When [1] SenS = Linear input: 0... 3.

• 

When [1] SenS is different from linear input: 0 or 1.

note: 

All changes to dP parameter setting produce a 
change to all parameters related with it (Set points, 
Proportional band, etc.).

[3] SSc - Initial scale read-out for linear inputs

Available: 

When a linear input is selected by [1] SenS.

range: 

-1999... 9999.

notes: 1. 

SSc allows the scaling of the analogue input to 
set the read-out value shown when the instrument 
detects the minimum measurable value. 
The instrument is able to display the measured 
value until it reaches a value of 5% lower than SSc, 
below which shows the Underrange message.

2. 

It is possible to set an initial scale read-out higher 
than the full scale read-out in order to obtain a 
reverse read-out scaling 

e.g.: 

0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum).

[4] FSc - Full scale read-out for linear input

Available: 

When a linear input is selected by [1] SenS.

range: 

-1999...  9999

notes: 1. 

Fsc allows the scaling of the analogue input to set 
the read-out value shown when the instrument 
detect the maximum measurable value.  
The instrument is able to display the measured 
value until it reaches a value of 5% higher than 
FSc, above which shows the Overrange message.

Summary of Contents for KX6 Series

Page 1: ...r permanent installation for indoor use only in an electrical panel which encloses the rear housing exposed terminals and wiring on the back Select a mounting location having the following characteris...

Page 2: ...0 mA input wiring for passive transmitter using an external power supply _ _ 1 2 0 4 20 mA Passive transmitter _ External PWS Input impedance 50W 0 4 20 mA input wiring for active transmitter 0 4 20 m...

Page 3: ...4 NO 9 C NO Alarm 1 OP3 Alarm 2 OP4 Load AC 8 10 Load Contact rating 2 A 250 V cosj 1 1 A 250 V cosj 0 4 Operation 1 x 105 2 4 Serial Interface RS 485 D D GND 17 18 16 D D GND D D GND D D GND Interfac...

Page 4: ...0 023 in Weight 160 g max Power supply 100 240 VAC 15 10 of the nominal value Power consumption 5 VA max Insulation voltage 2300 V rms according to EN 61010 1 Display updating time 500 ms Sampling tim...

Page 5: ...s to take advantage of all instrument features The instrument have one complete parameter set indicated as Configuration parameter set or Configuration parameters The access to the configuration param...

Page 6: ...buttons set the value 581 3 Push button 4 The instrument turns ON all the LEDs for a few seconds then returns to the Standard display mode Notes 1 If the instrument does NOT TURN ON ALL the LEDs for...

Page 7: ...out 2 output while the values greater than zero activate the Open valve out 1 output 4 When ON OFF control is programmed and an out of range is detected the instrument performs the safety output valu...

Page 8: ...tion low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the band LHdi Relative band alarm with alarm indication inside the band Notes 1 The rel...

Page 9: ...1010 mBar but this value is out of range The reset can be made only by turning the instrument OFF removing the condition that generate the alarm and then turn the instrument ON again All band alarms u...

Page 10: ...to 0 the tempera ture must go down if not the SSR is in short circuit the valve is jammed and so on So the LBA should be generated LBA function is automatically enabled when the PID requires the maxi...

Page 11: ...7 EvoTune with manual start 8 EvoTune with automatic restart at all set point change 41 tunE Manual start of the auto tune Available Always Range oFF The instrument is not performing the auto tune on...

Page 12: ...start time Available When 39 cont PID or 39 cont 3Pt and 58 Pot Pot c Range oFF Function not used 0 01 7 59 hh mm inF Soft start always active Note The time calculation starts at Power ON and is inte...

Page 13: ...Note For other details see 61 SPLL parameter 63 SP Set Point 1 Available Always Range From 61 SPLL to 62 SPHL engineering units 64 SP 2 Set Point 2 Available When 60 nSP 2 Range From 61 SPLL to 62 SP...

Page 14: ...The first press puts the in strument in stand by mode while a second one puts the instrument in Auto mode SP1 2 SP SP2 selection Notes 1 When SP1 2 is used every press of the button longer than 1 sec...

Page 15: ...ence between AL P and AH P is equal to 10 Engineering Units 87 AL o Adjust Low Offset Available Always Range 300 300 engineering units 88 AH P Adjust High Point Available Always Range From AL P 10 to...

Page 16: ...L2 Pb A 7 Pb ti A 8 ti td A 9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds The upper display will show PASS while the middle display shows 0 2 By and buttons se...

Page 17: ...assword Notes 1 The factory default password for configuration parameters is 20 2 Operator and assistace level of Parameter modification are protected by a time out If no button is pressed for more th...

Page 18: ...always on display and no button is pressed for more than the programmed time out the display goes OFF and only 4 segments of the less significant digit are turned ON in sequence in order to show that...

Page 19: ...lectrical equipment for measurement control and laboratory use for this reason it could not be used as a safety equipment Whenever a failure or a malfunction of the control device may cause dangerous...

Page 20: ...to use it ti configure other instruments To transfer a complete instrument configuration to a PC or from a PC to an instrument To transfer a complete instrument configuration from a PC to an instrumen...

Page 21: ...Digital Input 2 function oFF 11 di A Digital Inputs Action DI2 only if configured 0 DI1 direct action DI2 direct action 1 DI1 reverse action DI2 direct action 2 DI1 direct action DI2 reverse action 3...

Page 22: ...n stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in out of range condition 0 AL2 group no Param Description Dec Point Values Default 27 AL2t Alarm 2 t...

Page 23: ...ower up and after a set point change 5 Evo tune with automatic restart at every power up 6 Evo tune with automatic start the first power up only 7 Evo tune with manual start 8 Evo tune with automatic...

Page 24: ...nction tunE Auto tune self tune enabling A single press longer than 1 se cond starts the auto tune oPLo Manual mode The first pressure puts the instrument in manual mode oPLo while a second one puts t...

Page 25: ...ted Master nonE Retransmission not used the instrument is a slave rSP The instrument becomes a Master and retransmits the operative set point PErc The instrument become a Master and it retransmits the...

Page 26: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 26...

Page 27: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 27...

Page 28: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 28...

Reviews: