ser group - serial link parameters
no. param.
description
dec.
point
values
default
83
Add
Instrument address
- oFF;
- 1... 254.
1
84
bAud
Baud rate
1200 = 1200 baud;
2400 = 2400 baud;
9600 = 9600 baud;
19.2 = 19200 baud;
38.4 = 38400 baud
9600
85
trSP
Selection of the value to
be retransmitted (Master)
nonE = Retransmission not used (the instrument is a slave);
rSP =
The instrument becomes a Master and retransmits the operative set
point;
PErc = The instrument become a Master and it retransmits the power output
nonE
]
cAl group - user calibration parameters
no. param.
description
dec.
point
values
default
86
AL.P
Adjust Low Point
From -1999 to (AH.P - 10) in engineering units
0
87
AL.o
Adjust Low Offset
-300... +300 (E.U.)
0
88
AH.P
Adjust High Point
From (AL.P + 10) to 9999 engineering units
9999
89
AH.o
Adjust High Offset
-300... +300
0