Ascon Tecnologic - KX6 Series - ENGINEERING MANUAL -Vr. 0.0

 PAG. 1

KX6

Controller with 

servomotor drive output

engineering manual

Code : ISTR-MKX6ENG06 - Vr. 0.0 (ENG)

Ascon tecnologic s.r.l.

Viale Indipendenza 56, 27029 Vigevano (PV) - ITALY

tel.:

 +39 0381 69871/

FAX:

 +39 0381 698730

www.ascontecnologic.com

e-mail:

 

[email protected]

1.  outline dimensions (mm)

1.1  dimensions

48

89

11

KX6

96

89

1.2  pAnel Cutout

65 mm min.

45

+0.6

 mm

89

+0.8

 mm

113  mm min.

1.3  mounting requirements

This instrument is intended for permanent installation, for 
indoor use only, in an electrical panel which encloses the 
rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:

1. 

It should be easily accessible;

2. 

There is minimum vibrations and no impact;

3. 

There are no corrosive gases;

4. 

There are no water or other fluids (i.e. condensation);

5. 

The ambient temperature is in accordance with the 
operative temperature (0... 50°C);

6. 

The relative humidity is in accordance with the instrument 
specifications (20... 85%);

The instrument can be mounted on panel with a maximum 
thickness of 15 mm.
When the maximum front protection (IP65) is desired, the 
optional gasket must be mounted.

Summary of Contents for KX6 Series

Page 1: ...r permanent installation for indoor use only in an electrical panel which encloses the rear housing exposed terminals and wiring on the back Select a mounting location having the following characteris...

Page 2: ...0 mA input wiring for passive transmitter using an external power supply _ _ 1 2 0 4 20 mA Passive transmitter _ External PWS Input impedance 50W 0 4 20 mA input wiring for active transmitter 0 4 20 m...

Page 3: ...4 NO 9 C NO Alarm 1 OP3 Alarm 2 OP4 Load AC 8 10 Load Contact rating 2 A 250 V cosj 1 1 A 250 V cosj 0 4 Operation 1 x 105 2 4 Serial Interface RS 485 D D GND 17 18 16 D D GND D D GND D D GND Interfac...

Page 4: ...0 023 in Weight 160 g max Power supply 100 240 VAC 15 10 of the nominal value Power consumption 5 VA max Insulation voltage 2300 V rms according to EN 61010 1 Display updating time 500 ms Sampling tim...

Page 5: ...s to take advantage of all instrument features The instrument have one complete parameter set indicated as Configuration parameter set or Configuration parameters The access to the configuration param...

Page 6: ...buttons set the value 581 3 Push button 4 The instrument turns ON all the LEDs for a few seconds then returns to the Standard display mode Notes 1 If the instrument does NOT TURN ON ALL the LEDs for...

Page 7: ...out 2 output while the values greater than zero activate the Open valve out 1 output 4 When ON OFF control is programmed and an out of range is detected the instrument performs the safety output valu...

Page 8: ...tion low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the band LHdi Relative band alarm with alarm indication inside the band Notes 1 The rel...

Page 9: ...1010 mBar but this value is out of range The reset can be made only by turning the instrument OFF removing the condition that generate the alarm and then turn the instrument ON again All band alarms u...

Page 10: ...to 0 the tempera ture must go down if not the SSR is in short circuit the valve is jammed and so on So the LBA should be generated LBA function is automatically enabled when the PID requires the maxi...

Page 11: ...7 EvoTune with manual start 8 EvoTune with automatic restart at all set point change 41 tunE Manual start of the auto tune Available Always Range oFF The instrument is not performing the auto tune on...

Page 12: ...start time Available When 39 cont PID or 39 cont 3Pt and 58 Pot Pot c Range oFF Function not used 0 01 7 59 hh mm inF Soft start always active Note The time calculation starts at Power ON and is inte...

Page 13: ...Note For other details see 61 SPLL parameter 63 SP Set Point 1 Available Always Range From 61 SPLL to 62 SPHL engineering units 64 SP 2 Set Point 2 Available When 60 nSP 2 Range From 61 SPLL to 62 SP...

Page 14: ...The first press puts the in strument in stand by mode while a second one puts the instrument in Auto mode SP1 2 SP SP2 selection Notes 1 When SP1 2 is used every press of the button longer than 1 sec...

Page 15: ...ence between AL P and AH P is equal to 10 Engineering Units 87 AL o Adjust Low Offset Available Always Range 300 300 engineering units 88 AH P Adjust High Point Available Always Range From AL P 10 to...

Page 16: ...L2 Pb A 7 Pb ti A 8 ti td A 9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds The upper display will show PASS while the middle display shows 0 2 By and buttons se...

Page 17: ...assword Notes 1 The factory default password for configuration parameters is 20 2 Operator and assistace level of Parameter modification are protected by a time out If no button is pressed for more th...

Page 18: ...always on display and no button is pressed for more than the programmed time out the display goes OFF and only 4 segments of the less significant digit are turned ON in sequence in order to show that...

Page 19: ...lectrical equipment for measurement control and laboratory use for this reason it could not be used as a safety equipment Whenever a failure or a malfunction of the control device may cause dangerous...

Page 20: ...to use it ti configure other instruments To transfer a complete instrument configuration to a PC or from a PC to an instrument To transfer a complete instrument configuration from a PC to an instrumen...

Page 21: ...Digital Input 2 function oFF 11 di A Digital Inputs Action DI2 only if configured 0 DI1 direct action DI2 direct action 1 DI1 reverse action DI2 direct action 2 DI1 direct action DI2 reverse action 3...

Page 22: ...n stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in out of range condition 0 AL2 group no Param Description Dec Point Values Default 27 AL2t Alarm 2 t...

Page 23: ...ower up and after a set point change 5 Evo tune with automatic restart at every power up 6 Evo tune with automatic start the first power up only 7 Evo tune with manual start 8 Evo tune with automatic...

Page 24: ...nction tunE Auto tune self tune enabling A single press longer than 1 se cond starts the auto tune oPLo Manual mode The first pressure puts the instrument in manual mode oPLo while a second one puts t...

Page 25: ...ted Master nonE Retransmission not used the instrument is a slave rSP The instrument becomes a Master and retransmits the operative set point PErc The instrument become a Master and it retransmits the...

Page 26: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 26...

Page 27: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 27...

Page 28: ...Ascon Tecnologic KX6 Line ENGINEERING MANUAL Vr 0 0 PAG 28...