6.
Connecting
a
Power
Supply
N4X
air
‐
conditioning
units
required
a
dedicated
10A
Single
‐
phase
AC
power
supply
for
each
aircon
module.
Each
Aircon
module
has
a
dedicated
power
ingress
point
at
the
top
rear
of
the
chassis
with
a
matching
IEC
C19
locking
power
receptacle.
An
additional
10A
single
‐
phase
power
supply
is
required
for
the
internal
equipment
to
be
mounted
within
the
Armarac
enclosure.
This
power
ingress
point
is
at
the
bottom
rear
of
the
chassis
(left
or
right
side
to
suit)
or
can
be
set
up
with
dual/redundant
power
feeds
with
two
receptacles.
6.1
Internal
IEC
‐
C19
power
receptacles
Step
1
–
Remove
the
power
receptacle
Remove
the
upper
and
lower
Patch
Panel
Mounting
Trays
from
within
the
chassis
using
a
2.5mm
hex
key.
Remove
the
power
socket
shield
using
a
7mm
hex
socket.
Remove
the
plastic
closed
grommet
from
the
side
rear
of
the
chassis
covering
the
cable
entry
hole
provided
to
facilitate
power
cable
entry
to
that
power
receptacle.
Step
2
–
Terminate
the
power
feed
If
using
conduit,
terminate
your
gland
in
to
the
opening
provided
on
the
chassis
(1
‐
inch
diameter).
Route
the
cable
inside
the
Armarac
and
through
the
hole
on
the
side
of
the
power
socket
shield
Terminate
the
power
feed
on
to
supplied
IEC
C19
power
termination
socket
(maximum
rating
250V
16A).
Refit
the
power
socket
shield
to
the
Chassis
.
Refit
the
patch
panel
mounting
tray
to
the
chassis.