Armarac
MX800N4X
Series
Installation
Guide
v1.1
|
September
‐
2015
Page
10
of
56
3.
Recommended
Fastening
System
Anchoring
Systems
The
Armarac
wall
mount
bracket
is
designed
to
fasten
to
the
wall
with
two
vertical
columns
of
four
M8
(5/16in)
anchors
down
each
side,
spaced
horizontally
400mm
(16in)
centers.
Installation
to
a
wall
with
600mm
(24in)
vertical
centers
requires
the
optional
600mm
wall
mounting
adapters.
Note:
Please
drill
all
holes
using
the
chassis
as
the
template.
Substrate
Recommended
System
Wooden
Frame;
Carpentry
Hilti
HSL
Heavy
Duty
Anchor
HUS
‐
H
Universal
Screw
Anchor
Or
equivalent
such
as
SPAX
3.5”
bolts
for
wooden
walls
Masonry;
Concrete
Block,
Concrete
Slab
Brick
Hilti
HSL
Expansion
Anchor
(M8)
[note
suitable
for
brick]
Or
equivalent
Hilti
HIT
‐
HY
Series
Chemical
Anchor
System,
and
Hilti
HAS
Threaded
Anchor
Rod
(M8)
Or
equivalent
For
more
information
and
availability
see
www.hilti.com
When
using
the
Armarac
Support
Base;
four
(4)
M10
(3/8in)
anchors
should
be
used
to
secure
the
base
to
the
floor.
And
another
two
(2)
M8
(3/8in)
fasteners
to
secure
the
top
of
the
Armarac
chassis
to
the
wall
for
added
stability.
Refer
to
recommended
fastening
systems
above.
If
in
any
doubt
please
consult
with
an
engineer
as
to
the
best
anchoring
system
to
use
for
your
environment.