The output can be set to:
1)
OFF
(default)
2)
FLOW +
output ON, for any positive flow
3)
FLOW
–
output ON, for any negative flow
4)
ERROR
output ON, for any error identified by the device
5)
AIR DETECT
output ON, during air detection (empty pipe)
6)
FIXED
output ON, fixed status signal
7)
ON IN
output ON, if the actual flow is within the given range with hysteresis (can be set under
Comparator Flow - Flow 1, Flow 2, Hysteresis 1 and Hysteresis
8)
ON OUT
output ON, if the actual flow is outside the given range with hysteresis (can be set under
Comparator Flow - Flow 1, Flow 2, Hysteresis 1 and Hysteresis 2)
9)
ON > Flow1
output ON, if the actual flow is the bigger than the value set as Flow 1 and hysteresis
(can be set under Comparator Flow
– Flow 1, Hysteresis 1)
10)
ON < Flow1
output ON, if the actual flow is smaller than the value set as Flow 1 and hysteresis
(can be set under Comparator Flow
– Flow 1, Hysteresis 1)
11)
VOLUME PULSE
– the output generates a pulse when the preset volume has passed the sensor
(the pulse width can be set). The battery current consumption is higher if you choose this option. Minimal
resolution is 1m3.
Option 11 is battery consumable!
On In:
On Out:
On > F
1
:
On < F
1
:
Pulse Width
–
width of the generated pulse in ms (1
– 999 ms).
ON
OFF
F
1
F
1
+ H
1
F
2
– H
2
F
2
ON
OFF
F
1
F
1
+ H
1
F
2
F
2
– H
2
ON
OFF
F
1
F
1
+ H
1
ON
OFF
F
1
F
1
+ H
1