13.3.6. Process of an evacuation travel:
The elevator controller must be capable of performing an evacuation operation in case of a power
failure. The following operations must be carried out respectively by the elevator control system:
●
Control detects mains failure.
●
Control recognizes inverter fault.
●
Control waits a certain time for the mains power to restore or for a generator to go online.
●
Control disconnects the mains supply from inverter by releasing the KSAK contactor.
●
Control activates the KKAK contactor after a certain time (
t1
: minimum 2s):
▪
This connects the back-up power supply to the input terminals L1 and L3.
▪
This activates the input terminal CI1. Inverter goes into an evacuation operation mode and
inverter fault is cleared.
●
Control recognizes that the inverter is ready (no fault).
●
Control activates the drive ENABLE signal (input terminal EN) by activating the main
contactors (KPA and KPB).
●
Control applies the speed and direction command to the inverter.
▪
If the parameter “12.2-DIRECTION” is set as “BD: EASIEST DIR”:
◦
Inverter ignores the applied speed and direction commands and starts running the
motor in the optimum direction (easy direction) with a maximum speed limited with V4
speed.
▪
If the parameter “12.2-DIRECTION” is set as “BD: COMMAND DIR”:
◦
Inverter ignores only the applied speed command and starts running the motor in the
direction applied with a maximum speed limited with V4 speed.
●
Control deactivates the evacuation operation after the trip is completed with the following
sequence:
▪
Control releases the KKAK contactor:
◦
This disconnects the back-up power supply from the inverter.
◦
This deactivates the input terminal CI1. Inverter goes into a normal operation mode.
▪
Control reconnects the mains power to the inverter by activating the KSAK contactor after
a certain time (
t2
: minimum 1s).
Mains power failure
t1
t2
KSAK
KKAK
EN
UP/DWN
Vx (V0/V1/V2/V3)
AC supply
mode
Evacuation mode
AC supply
mode