0040501006 3814
Page 2-37
Operating and installation instructions
Thrust actuator ARI-PREMIO
®
-Plus 2G
5.7.2 Analogue output card - Y
out
Scope of suply:
5.7.2.1 Operating principle
The actual position of the driving spindle can be signalled with the analogue output card.
The connector for the output signal is already mounted on the motherboard.
The feedback signal (4 to 20 mA, 0 to 10 V or inverted) corresponds to the switch configuration on
the motherboard.
The characteristic correction function has
no effect
on the output signal
5.7.2.2 Technical data
Pcs.
Designation
1
Analogue output card
2
PT screws
Fig. 21
Type
Analogue output card - Y
out
Output control signal Y
U
0 -10V DC
- Measuring resistance (load): max. 2 kohm
- Signal resolution: 12 Bit
Output control signal Y
I
4 -20mA DC, active
- Measuring resistance (load): max. 500 ohm
- Signal resolution:12 Bit