Operating and installation instructions
Thrust actuator ARI-PREMIO
®
-Plus 2G
4.5.3 Design notes
4.5.3.1 Control signal
- At the 4-20mA signal, from a control signal <3.6 mA, control signal failure will be detected.
- A cable break is detected in both the current signal 4-20mA as well as the voltage signal 0-10V.
- The control signal range is fixed from 0-10V, resp. 4-20mA. From software version 3.x.x upwards it
is possible to set alternatively the voltage signal for auf 2-10V via the diagnostics interface and
PC. The 2-10V then apply also for the feedback signal. A diagnostics connector and instructions
can be ordered on request.
- The 3 point control signal has a higher priority than the analogue control signal. This can for
example be used for frost protection or a local control.
In a concurrent control in direction OPEN and CLOSED, over the 3-point control signal, the motor
stops, so that the drive no longer follows the analogue input signal.
- The switch positions for control signal type and inversion affects to the analogue input and
feedback signal. There are no separate settings for the input and feedback signal possible.
Warning signal
- Manual operating
device
- Blockage (detected)
- Position cannot be
achieved
- Maintenance
- Inside temperature
exceeded
- CDF-Managment active
- Leveling
- too small travel during
initialization
Change over contact
30V AC/DC 2A
- Relay card ARI-PREMIO
®
-Plus 2G
Modbus
- Protocol: Modbus, Modbus-
integer
- Baud rate: 9600, 19200, 38400
- Device address: 0 ... 255
- Max. number of participants: 32
- Relay card ARI-PREMIO
®
-Plus 2G
-
dTRON 316
with RS422/485 card and at more than 2
binary feedbacks the binary input card is
required (dTRON options)
Profibus-DP
- Device address: 0 ... 255
- Relay card ARI-PREMIO
®
-Plus 2G
-
dTRON 316
with Profibus card and at more than 2
binary feedbacks the binary input card is
required (dTRON options)