0040501006 3814
Operating and installation instructions
Thrust actuator ARI-PREMIO
®
-Plus 2G
5.7.4 Power supply
5.7.4.1 Installation and connection of the power supply
Fig. 26: Installtation and connection of the power supply ARI-PREMIO
®
-Plus 2G 2,2-15 kN
5.7.5 Integrated temperature controller dTRON 316
The integrated temperature controller controls temperatures, which are measured by
inputconnected temperature sensors, to a manual given setpoint by means of a three-step output
connected with the actuator.
5.7.5.1 Installation of the dTRON 316
The dTRON 316 can be mounted in the ARI-PREMIO
®
-Plus 2G as a complete unit with a mounting
kit.
To install the dTRON 316 proceed as follows:
In addition to „5.4 Electrical connection“, the electrical connection of the dTRON 316 has to be done
in the following way:
-
Mount the temperature controller on the gear plate by using the specific installation kit
- Plug in the connector X25 of the dTRON 316 to the plug-in connector X59 (0V / L
/ L
) of the
actuator terminal.
- Connect the signal input and the individual wanted additional functions according to the wiring
diagram to the dTRON 316.
- Connect the power supply L1 and N to the dTRON 316.
- For changing the working direction to heating signal = extending driving spindle, just change the
wires on the connectors L
and L
.