Page 2-11
Operating and installation instructions
Thrust actuator ARI-PREMIO
®
-Plus 2G
4.5 Interface description
4.5.1 Control - Run commands
Control
Desciption - Technical data
Required options
OPEN-STOP-CLOSE
(3-point)
2 Binary input
- 12V AC/DC to 250V AC/DC
-
Modbus
- Protocol: Modbus, Modbus-integer
- Baud rate: 9600, 19200, 38400
- Device address: 0 ... 255
- Max. number of participants: 32
-
dTRON316
with RS422/485 card
(dTRON options)
Profibus-DP
- Device address: 0 ... 255
-
dTRON316
with Profibus card (dTRON options)
Set point control for
position controller
4-20mA DC
- Burden 125 Ohm
- Resolution 10 Bit
- Electrically isolated
-
0-10V DC
- Burden 500 kOhm
- Resolution 10 Bit
- Electrically isolated
-
Modbus
- Protocol: Modbus, Modbus-integer
- Baud rate: 9600, 19200, 38400
- Device address: 0 ... 255
- Max. number of participants: 32
-
dTRON316
with analogue output card and
RS422/485 card (dTRON options)
Profibus-DP
- Device address: 0 ... 255
-
dTRON316
with analogue output card and
Profibus card (dTRON options)
Sollwert Ansteuerung
für PID-Prozessregler
(Option dTRON 316)
4-20mA DC
- Burden 75 Ohm
- Resolution 10Bit
-
dTRON316
with analogue output card and
analogue input card (dTRON options)
0-10V DC
- Burden > 100 kOhm
- Resolution 10 Bit
-
dTRON316
with analogue output card and
analogue input card (dTRON options)
Modbus
- Protocol: Modbus, Modbus-integer
- Baud rate: 9600, 19200, 38400
- Device address: 0 ... 255
- Max. number of participants: 32
-
dTRON316
with analogue output card and
RS422/485 card (dTRON options)
Profibus-DP
- Device address: 0 ... 255
-
dTRON316
with analogue output card and
Profibus card (dTRON options)