![ARI-Armaturen ARI-PACO 2G 1,6 D Operating And Installation Instruction Download Page 27](http://html1.mh-extra.com/html/ari-armaturen/ari-paco-2g-1-6-d/ari-paco-2g-1-6-d_operating-and-installation-instruction_2969564027.webp)
0040506004 0919
Page 2-27
Operating and installation instructions
Thrust actuator ARI-PACO
®
2G 1,6D/Y
Rpm / operating speed
adjustment
Configuration switches for the analogue control signal
Voltage
This slide switch
Y
can be used to select a 0 to 10 V or 2 to 10 V
voltage signal. The setting applies to both the control signal input
and output.
Invert control signal
This slide switch inverts the analogue control signal (input and
output).
Switch up:
Inverted: 0V or 2V = driving spindle retracted
Switch down
:
Normal: 0V or 2V = driving spindle extended
Fail-safe behaviour in
case of control signal
failure
In case of a control signal failure or a cable break (0-10 V and 2-10
V) the set position is approached:
·
End position UP
·
STOP
·
End position DOWN
Switch
Meaning
Description / explanation
Stufe
ARI-PACO
®
2G 1,6kN
3
2600 U/min
1,00 mm/sec
2
1250 U/min
0,47 mm/sec
1
1000 U/min
0,38 mm/sec
0
660 U/min
0,25 mm/sec (default)