VP5000-DC/DC60, VP5000-DC/DC200-HL
Installation and commissioning
Last edited 2019-02-08
by Sonja Scheunert
Filename
VP5000_DCDC60_200-HL_installation_manual_v1-4en.docx
130 / 173
Figure 99: [DC+/-] and [/-] connections
on the VECTOPOWER VP5000-DC/DC200-HL
Connect [DC+/-] and [/-]:
•
The position of the connections is shown
in the adjacent figure. The connections
are labeled on the housing.
Figure 100: Connection of a power wire to the
terminal block
8.
Open the screw (3).
9.
Insert the corresponding wire through the
double nipple (2) in the housing.
•
When connecting, observe the polarity
(+/-) of the respective connection.
10.
Place the cable lug (5) on the terminal
block.
Figure 101: Installation examples: Screw
connections with wedge lock washer, source: Nord-
Lock data sheet
11.
Insert the screw (3) with a pair of Nord-
Lock wedge lock washers (4).
12.
Tighten the screw (3) with 15 Nm /
132.8 inlb.
Figure 102: Example of EMC cable gland (Pflitsch,
blueglobe TRI type)
13.
Screw the pressure screw (6) to the
double nipple (2) on the housing. (Here
shown using the example of an EMC cable
gland from Pflitsch, blueglobe TRI type.)
14.
Tighten the pressure screw (6) with the
torque specified by the manufacturer.
15.
Repeat the procedure until all connections
for [DC+/-] and [/-] are
connected.