Do not pass water through the UV system for a minimum of 5 minutes after applying power (including after power interruptions) to avoid passing 
under-treated water that may, in rare instances, pose health hazards.

  •

Changes or modifications made to this system without the consent of the manufacturer could render the system unsafe for operation and may void the 
manufacturer's warranty. 

C A U T I O N

1.3 Water Chemistry

Water quality is extremely important for the optimum performance of your UV system. The following levels are 
recommended for installation:

* Where total hardness is less than 7 gpg, the UV unit should operate efficiently provided the quartz sleeve is cleaned 
periodically. If total hardness exceeds 7 gpg, the water should be softened. If your water chemistry contains levels in excess 
of those mentioned above, proper pre-treatment is recommended to correct these water problems prior to the installation of 

WA R N I N G

  •

During extended periods of no water flow, the water in your chamber can become very hot (Approx. 60 °C) and potentially lead to scalding. It is 
recommended to run your water until this hot water has been purged from your chamber. Do not allow water to contact your skin during this time. To 
eliminate this condition, a temperature management valve can be installed at the outlet of your UV system.

  •

This system contains a UV Lamp. Do not operate the UV Lamp when it is removed from the chamber. Unintended use or damage of the system may 
result in the exposure of dangerous UV radiation. UV radiation may, even in little doses, cause harm to the eyes and skin.

WARNING:

 This product can expose you to chemicals including phthalates, which is known to the state of California to cause cancer, and mercury, which 

is known to the State of California to cause birth defects or other reproductive harm. For more information go to 

www.P65Warnings.ca.gov

.

Failure to follow these instructions could result in minor or moderate injury.

  •

Carefully examine the disinfection system after installation. It should not be plugged in if there is water on parts not intended to be wet such as, the 
controller or lamp connector.

  •

Due to thermal expansion concerns and potential material degradation due to UV exposer, it is recommended to use metal fittings and at least 10” 
of copper pipe on the outlet of your UV chamber.

  •

Hg EXPOSURE

: The UV lamp contains mercury. If the lamp breaks, then avoid inhalation or ingestion of the debris and avoid exposure to eyes and 

skin. Never use a vacuum cleaner to clean up a broken lamp as this may scatter the spilled mercury. Obey local regulations and guidelines for the 
removal and disposal of mercury waste.

N O T I C E

  •

The UV lamp inside the disinfection system is rated at an effective life of approximately 9000 hours. To ensure continuous protection, replace the 
UV lamp annually.

  •

The UV system is not to be used or played with by children. Persons with reduced physical, sensory or mental capabilities, or lack of experience 
and knowledge, are also not to handle the UV system unless they have been given supervision or instruction. 

  •

This system is intended to be permanently connected to the water lines.

  •

This system is not intended to be used in or above water or outdoors or used in swimming pools when persons are in the pool.

  •

EXTENSION CORDS

: If an extension cord is necessary, use only 3-wire extension cords that have 3-prong grounding-type plugs and 3-pole cord 

connectors that accept the plug from this system. Use only extension cords that are intended for outdoor use. Use only extension cords having an 
electrical rating not less than the rating of the system. A cord rated for less amperes or watts than this system rating may overheat. Exercise caution 
when arranging the cord so that it will not be tripped over or pulled. DO NOT use damaged extension cords. Examine extension cord before using 
and replace if damaged. DO NOT abuse extension cord. Keep extension cord away from heat and sharp edges. Always disconnect the extension 
cord from the receptacle before disconnecting this system from the extension cord. Never yank cord to pull plug from outlet. Always grasp the plug 
and pull to disconnect.

  •

If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.

  •

SYSTEM PROTECTION:

 To protect your Controller, a UL1449 certified (or equivalent) transient voltage surge suppressor is strongly 

recommended.

  •

The UV lamp in this system conforms to the applicable provisions of the Code of Federal Regulations (CFR) requirements including, Title 21, 
Chapter 1, Subchapter J, Radiological Health.

  •

Read and understand the Owner’s Manual before operating and performing any maintenance on this equipment.

Water Quality and Minerals

Level

Iron

< 0.3 ppm (0.3 mg/L)

Hardness*

< 7 gpg (120 mg/L)

Turbidity

< 1 NTU

Manganese

< 0.05 ppm (0.05 mg/L)

Tannins

< 0.1 ppm (0.1 mg/L)

UV Transmittance

> 75% (call factory for recommendations on applications where UVT < 75%)

UV

Hg

Safety Information

4

Summary of Contents for SC200-A

Page 1: ...Owner s Manual Powered by Models SC200 A SC410 A 520192 R_RevK...

Page 2: ...should you insist on genuine factory supplied VIQUA replacement lamps Use of widely available non genuine replacement lamps has been shown to damage the control module of VIQUA UV disinfection equipme...

Page 3: ...l for VERY hot water when flow is started 1 2 Safety Precautions DANGER Electric Shock To avoid possible electric shock special care should be taken since water is present near the electrical equipmen...

Page 4: ...n avoid inhalation or ingestion of the debris and avoid exposure to eyes and skin Never use a vacuum cleaner to clean up a broken lamp as this may scatter the spilled mercury Obey local regulations an...

Page 5: ...1 O ring 410867 Used on all systems 2 214 fused quartz sleeves with fire polished ends QS 001 SC200 A QSO 410 SC410 A 3 Retaining Nut RN 001 Used on all systems 4 Hard glass coated Sterilume HO UV la...

Page 6: ...5 micron sediment filter must precede the disinfection system Ideally the disinfection system should be the last treatment the water receives before it reaches the faucet Procedure 1 The use of a by...

Page 7: ...nection point to prevent any water from potentially leaking onto the controller by means of a leak at a connection point or a sweating system Make sure you allow for a drip loop as shown in Figure 5 o...

Page 8: ...2 1 2 2 2 Shut off the water supply Close each faucet 3 1 2 Remove filter cartridge s 4 Household 5 25 Bleach Solution BLEACH x2 2 Pour 2 cups of household bleach solution into the filter housing s No...

Page 9: ...main power source and allow the unit to cool for 10 minutes 3 1 2 Remove the lamp connector by squeezing the plastic locking tabs on the side of the connector 4 Hg UV Remove the lamp in upward directi...

Page 10: ...then replace the sleeve 6 Reinstall the quartz sleeve in the chamber allowing the sleeve to protrude an equal distance at both ends of the chamber Slide supplied O rings onto each end of the quartz sl...

Page 11: ...refer to Section 4 1 5 1 3 Resetting Lamp Life Refer to Section 4 1 Note Even though the alarm on the system can be deferred for a period of time it is important to address each and every alarm condit...

Page 12: ...system must have a bacterial free distribution system to work effectively Refer to Section 3 1 Possible break through of sediment through pre filter Have source water tested for turbidity may need st...

Page 13: ...1 MNPT 3 4 FNPT Combo 3 4 FNPT 1 MNPT Shipping Weight 5 1 kg 11 3 lbs 6 8 kg 15 0 lbs Electrical Voltage 100 240 V 50 60Hz 100 240 V 50 60Hz Max Current 1 5 Amp 1 5 Amp Power Consumption 35 W 60 W La...

Page 14: ...rdware Components VIQUA warrants the electrical controller and hardware components to be free from defects in material and workmanship for a period of three 3 years from the date of purchase During th...

Page 15: ...Supporter par Mod les SC200 A SC410 A Manuel d utilisation Supporter par 520192 R_RevK...

Page 16: ...ine VIQUA Il a t d montr que l utilisation de lampes de rechange qui ne sont pas d origine et largement disponibles endommage le module du dispositif de commande du syst me de d sinfection par UV VIQU...

Page 17: ...nnect une prise correctement mise la terre prot g e par un disjoncteur de fuite de terre DFT Ce symbole indique qu il y a un risque potentiel d eau TR S chaude lorsque l coulement commence DANGER Le n...

Page 18: ...mercure Si la lampe se brise vitez d inhaler ou d ing rer des d bris ou m me d exposer vos yeux et votre peau N utilisez jamais d aspirateur pour nettoyer une lampe bris e car cela pourrait r pandre l...

Page 19: ...0867 Utilis sur tous les syst mes 2 manchons en quartz fondu 214 avec extr mit s polies au feu QS 001 SC200 A QSO 410 SC410 A 3 crou de blocage RN 001 Utilis sur tous les syst mes 4 Lampes UV en verre...

Page 20: ...e de d sinfection devrait tre le dernier traitement re u par l eau avant qu elle arrive au robinet Proc dure 1 L utilisation d un ensemble de d rivation est recommand e dans le cas o le syst me n cess...

Page 21: ...tif de commande 5 Installez la lampe UV Consultez la Section 4 1 6 Lorsque tous les raccords de plomberie sont termin s tournez lentement l alimentation en eau et v rifiez les fuites ventuelles La cau...

Page 22: ...ra nera l oxydation de ces contaminants et pourrait n cessiter le rin age r p t du r servoir d eau chaude Cette ventualit doit tre trait e ind pendamment selon la proc dure de d marrage pour tout autr...

Page 23: ...mplacement de la lampe UV 1 Couper la canalisation d eau vers la chambre et rel cher la pression du syst me avant de proc der l entretien 2 0 30 15 45 10 min D brancher la source d alimentation princi...

Page 24: ...age inf rieur le ressort flottant et le joint torique 3 1 2 D poser l crou de blocage sup rieur et le joint torique 4 D poser le manchon de quartz 5 Mild Acid Nettoyer le manchon en quartz avec un chi...

Page 25: ...teur consultez la Section 4 1 5 1 3 R initialisation de la dur e de vie de la lampe Consultez la Section 4 1 Remarque m me si l alarme du syst me peut tre report e pendant un certain temps il est impo...

Page 26: ...st en place recherchez des coupures ou usures nettoyez le joint torique humidifiez le l eau lubrifiant et reposez le remplacez le si n cessaire 410867 Condensation sur la chambre UV caus e par une hum...

Page 27: ...Courant max 1 5 amp res 1 5 amp res Consommation lectrique 35 W 60 W Watts de la lampe 25 W 45 W Pression maximale de fonctionnement 125 psi 861 kPa 125 psi 861 kPa Pression minimale de fonctionnemen...

Page 28: ...VIQUA garantit les composants mat riels et lectriques dispositif de commande contre tout d faut de mati re et de main d uvre pour une dur e de trois 3 ann es compter de la date d achat Dans cette p ri...

Page 29: ...Desarrollado por Modelos SC200 A SC410 A Manual del propietario Desarrollado por 520192 R_RevK...

Page 30: ...eposici n VIQUA originales de f brica Se ha demostrado que el uso de las l mparas de reposici n no originales disponibles ampliamente en el mercado da a el m dulo de control del equipo de desinfecci n...

Page 31: ...UY caliente cuando se inicie el flujo PELIGRO El incumplimiento de estas instrucciones puede ocasionar lesiones graves o la muerte Descarga el ctrica Para evitar posibles descargas el ctricas se deben...

Page 32: ...ercurio En caso de rotura evite inhalar o ingerir los restos y evite la exposici n de ojos y piel Nunca utilice una aspiradora para limpiar una l mpara rota ya que podr a dispersar el mercurio vertido...

Page 33: ...go QS 001 SC200 A QSO 410 SC410 A 3 Tuerca de retenci n RN 001 Se utiliza en todos los sistemas 4 L mparas UV Sterilume HO revestido de cristal duro para una vida til prolongada y de calidad constante...

Page 34: ...i n deber a ser el ltimo tratamiento que reciba el agua antes de llegar al grifo Procedimiento 1 Se recomienda el uso de un conjunto de desv o en el caso de que el sistema requiera mantenimiento fuera...

Page 35: ...sulte Secci n 4 1 6 Cuando se hayan realizado todas las conexiones de tuber as conecte el suministro de agua lentamente y compruebe si hay fugas La causa m s probable de fugas est en la junta t rica E...

Page 36: ...a la oxidaci n de dichos contaminantes y es posible que sea necesaria una limpieza repetida del tanque de agua caliente Esta eventualidad se debe tratar de forma independiente bajo el procedimiento de...

Page 37: ...y libere la presi n del sistema antes de realizar el servicio 2 0 30 15 45 10 min Desconecte la fuente de alimentaci n principal y deje que la unidad se enfr e durante 10 minutos Desconecte la fuente...

Page 38: ...junta t rica de la parte inferior 3 1 2 Quite la tuerca de retenci n y la junta t rica de la parte superior 4 Quite la vaina tubular de cuarzo 5 Mild Acid Limpie la vaina tubular de cuarzo con un tra...

Page 39: ...onsulte la Secci n 4 1 5 1 3 Reinicio de la vida de la l mpara Consulte Secci n 4 1 Nota Aunque la alarma del sistema se puede aplazar durante un per odo de tiempo es importante que se responda a toda...

Page 40: ...retenci n o el sensor UV Aseg rese de que la junta t rica est en su sitio compruebe si hay cortes o abrasiones l mpiela humed zcala con agua o lubricante y vuelva a instalarla o sustit yala si es nec...

Page 41: ...ltaje 100 240 V 50 60 Hz 100 240 V 50 60 Hz Corriente m xima 1 5 Amp 1 5 Amp Consumo de energ a 35 W 60 W Vatios de la l mpara 25 W 45 W Presi n m xima de funcionamiento 125 psi 861 kPa 125 psi 861 kP...

Page 42: ...ponentes el ctricos controlador y de hardware estar n libres de defectos de material y mano de obra durante un per odo de tres 3 a os desde la fecha de compra Durante este per odo VIQUA reparar o reem...

Page 43: ...43 Esta p gina est en blanco de forma intencional...

Page 44: ...25 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 tf 1 800 265 7246 US et Canada seulement t 31 73 747 0144 Europe seulement f 1 519 763 5069 Courriel info viqua com www viqua com 425 Clair...

Reviews: