Page - 71
Heat Pump Is Running, Not Heating
ISSUE
The heat pump is running. But the water is not heating.
RESOLUTION
1. If the heat pump is using an external controller, confirm it is set correctly.
l
Contact the installer of the device or the device’s manufacturer for further assistance.
2. Confirm heat pump mode is set to heat.
3. Confirm thermostat is set to the desired water temperature.
4. Confirm valves are positioned to heat the correct body of water (either the pool or the spa). If heating a
spa that overflows into a pool, confirm the spa is isolated when being heated (not flowing into the
pool).
5. Confirm heat pump is transferring heat into the water.
l
Measure the pool-side and source-side discharge water coming out of the heat pump.
l
Adjusting Water Flow Using ΔT (Delta-T)
6. If an error code is displayed, diagnose and correct cause of code.
l
7. Confirm that the filter pump has a sufficient run-time. The heat pump will not run (or heat the
water) without water flow.
l
8. If heating a spa, deactivate air blower or venturi (if equipped) to allow for quicker heating times. For
pools, deactivate water features, such as slides, waterfalls, or fountains to allow water to retain heat.
Use of a liquid pool blanket product, such as an Aqua Blanket
™
, can also compensate for excessive
heat loss.
l
Heat Pump Is Running, Not Cooling
ISSUE
The heat pump is running. But the water is not cooling.
RESOLUTION
1. If the heat pump is using an external controller, confirm the heat pump is programmed properly to
allow for cooling.
2. Confirm the heat pump mode is set to cool.
3. Confirm the thermostat is set below the current water temperature.
4. Confirm valves are positioned to cool the correct body of water (either the pool or the spa). If cooling a
spa that overflows into a pool, confirm the spa is isolated when being cooled (not flowing into the
pool).
5. If an error code is displayed, determine and correct the condition causing the code.
l
6. Confirm heat pump is transferring heat out of the water.
l
Measure the temperature of source-side and pool-side discharge water coming out of the heat pump.
l
Adjusting Water Flow Using ΔT (Delta-T)
7. Confirm that the filter pump has a sufficient run-time. The heat pump will not run (or cool the
water) without water flow.
l
Ice Forming on the Heat Pump
2
-
T
roubl
es
hoot
ing
Summary of Contents for AutoPilot SP05
Page 2: ......
Page 9: ...Page 5 Water Source Top View Water Source Side View 1 Installation...
Page 10: ...Page 6 1 3 Dimensions Water Source WS03 WS05 Water Source WS10 1 Installation...
Page 31: ...Page 27 Configure Call Flex Enter Installer Menus then proceed 1 Installation...
Page 32: ...Page 28 1 Installation...
Page 36: ...Page 32 1 Installation...
Page 39: ...Page 35 1 Installation...
Page 43: ...Page 39 1 Installation...
Page 44: ...Page 40 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation...
Page 48: ...Page 44 1 Installation...
Page 50: ...Page 46 1 Installation...
Page 53: ...Page 49 1 Installation...
Page 56: ...Page 52 1 Installation...
Page 58: ...Page 54 1 Installation...
Page 61: ...Page 57 1 Installation...
Page 63: ...Page 59 1 Installation...
Page 83: ...Page 79 l Follow all National Electric Codes NEC and or State and Local guidelines 3 Appendix...
Page 88: ......
Page 89: ......