Page - 24
Example of heat pump
transformer
(Varies between models)
1. Turn heat pump on by adjusting the thermostat to call for heating or cooling.
If more than one heat pump is on-site, turn them all on. Allow time for all
heat pump compressors to activate.
2. Measure the running site voltage.
3. Confirm transformer tap is set for the measured site voltage. If more than one
voltage tap is shown, select the voltage nearest to the running site voltage.
PLEASE NOTE -
l
If more than one voltage is shown on the equipment’s data plate, the factory default setting is
usually the higher voltage on the transformer.
l
As an example, a "208/230" voltage will be set to "240" from the factory.
1
-
Ins
ta
ll
at
ion
Summary of Contents for AutoPilot SP05
Page 2: ......
Page 9: ...Page 5 Water Source Top View Water Source Side View 1 Installation...
Page 10: ...Page 6 1 3 Dimensions Water Source WS03 WS05 Water Source WS10 1 Installation...
Page 31: ...Page 27 Configure Call Flex Enter Installer Menus then proceed 1 Installation...
Page 32: ...Page 28 1 Installation...
Page 36: ...Page 32 1 Installation...
Page 39: ...Page 35 1 Installation...
Page 43: ...Page 39 1 Installation...
Page 44: ...Page 40 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation...
Page 48: ...Page 44 1 Installation...
Page 50: ...Page 46 1 Installation...
Page 53: ...Page 49 1 Installation...
Page 56: ...Page 52 1 Installation...
Page 58: ...Page 54 1 Installation...
Page 61: ...Page 57 1 Installation...
Page 63: ...Page 59 1 Installation...
Page 83: ...Page 79 l Follow all National Electric Codes NEC and or State and Local guidelines 3 Appendix...
Page 88: ......
Page 89: ......