WIRING
WARNING
120 volts may cause serious injury from electrical shock. Sudden operation
may cause serious injury from moving parts. Leave power disconnected
until installation is complete.
Follow these steps for all system connections. Wiring will vary depending on
equipment.
Wiring of the zone panel must comply with applicable codes, ordinances and
regulations.
• Use only 18 or 20 gauge solid (
non-stranded
) wire.
• Strip off 7/16" of insulation from the wire.
• Push wire into the terminal of the zone panel.
• To release the wire, press down on the top of the terminal and pull the wire out.
• The zone panel supports multiple options to route and anchor wires to the
housing. See
FIGURE 6
.
WIRE TIE MOUNTS
90-2073
FIGURE 6
– WIRE TIE MOUNTS