MODEL 8052 TEMP SENSOR 

90-2087

FIGURE 10 

– DISCHARGE AIR TEMPERATURE SENSOR

DISCHARGE AIR TEMPERATURE SENSOR (INCLUDED)

•  Wire the discharge air temperature sensor 

Model 8052 to the “DAT” terminals as 
shown. See 

FIGURE 10

.

•  Maximum distance of the sensor from the 

zone panel is 300 feet.

•  Do not wire along 120VAC lines.

•  Refer to 

FIGURE 5

 on page 5 for the proper 

mounting location of the discharge air 
temperature sensor.

THERMOSTAT TERMINAL DEFINITIONS

R

 – 24VAC power to thermostat

C

 – 24VAC power to thermostat

W

 – Heating

Y

 – Cooling

G

 – Fan

NOTE:

Heat/cool thermostats must be used for all zones.

FURNACE AND A/C

HVAC TERMINAL DEFINITIONS

Y1

 – First stage cooling

W1

 – First stage heating

G

 – Fan

BOILER AND A/C

HVAC TERMINAL DEFINITIONS

Y1

 – First stage cooling

W1

 – First stage boiler heat

G

 – Fan

JUMPER

R

W1

G

Y1

FURNACE AND A/C

RC
W
Y
G

RH

HV

AC

Y1

G

R

BOILER AND A/C

R
C

W

BOILER

INDOOR AIR

HANDLER

AND A/C

RC
W
Y
G

RH

HV

AC

90-2115

90-2114

FIGURE 11 

– FURNACE AND A/C

FIGURE 12 

– BOILER AND A/C

HVAC TERMINAL DEFINITIONS

RH

 – 24VAC from heating equipment

RC

 – 24VAC from cooling equipment

W

 – Heating

Y

 – Cooling

G

 – Fan

9

B2206668C 61001213 AA 6202-6203 Zoned Comfort Control Install ENG-wrf.indd   9

6/14/18   3:28 PM

Summary of Contents for Zoned Comfort Control 6202

Page 1: ...READ AND SAVE THESE INSTRUCTIONS Model 6203 6202 Zoned Comfort Control Safety Installation Instructions B2206668C 61001213 AA 6202 6203 Zoned Comfort Control Install ENG wrf indd 1 6 14 18 3 28 PM...

Page 2: ...cooling system is properly sized and balanced 5 Insufficient air flow or excessive temperatures through the heating and cooling system could result in equipment damage Refer to the manufacturer s rec...

Page 3: ...IGURE 1 8 63 219 9 66 245 1 86 47 ZONE CONTROL 90 2108 FIGURE 1 ZONE PANEL DIMENSIONS IN INCHES mm APPLICATION ACCESSORIES APPLICATION The Model 6203 and 6202 Zone Panels are for conventional heat coo...

Page 4: ...12 COOLING Green Cooling is active Flashing DAT low temperature limit reached 13 FAN Green Fan output is active 14 ZONE 1 Green Damper is open Red Damper is closed 15 ZONE 2 Green Damper is open Red D...

Page 5: ...HVAC equipment Locate the panel on an interior wall stud or return duct See FIGURE 5 2 Locate the Discharge Air Temperature DAT in the supply trunk downstream of the heat exchanger and cooling coils...

Page 6: ...ly with applicable codes ordinances and regulations Use only 18 or 20 gauge solid non stranded wire Strip off 7 16 of insulation from the wire Push wire into the terminal of the zone panel To release...

Page 7: ...one panel and thermostats Example If you have a 3 zone system and there are two dampers per zone then the total number of dampers that could be energized at one time is 6 2 4 dampers 4 dampers x 10VA...

Page 8: ...ed damper For power open and power close dampers this terminal is used to power open the damper NO This terminal is used to power close a normally open damper For power open and power close dampers th...

Page 9: ...ermostat W Heating Y Cooling G Fan NOTE Heat cool thermostats must be used for all zones FURNACE AND A C HVAC TERMINAL DEFINITIONS Y1 First stage cooling W1 First stage heating G Fan BOILER AND A C HV...

Page 10: ...to the zone panel for heating the zone panel will initiate a heating call to the equipment and close the damper for all zones that are not calling for heat Following a 2 minute minimum on time the hea...

Page 11: ...OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED THIS LIMITED WARRANTY IS VOID IF DEFECTS S RESULT FROM FAILURE TO HAVE THIS UNIT INSTALLED BY A QUALIFIED HEATI...

Page 12: ...1467 Madison WI 53701 1467 800 334 6011 F 608 257 4357 2018 Aprilaire Division of Research Products Corporation 61001213 B2206668C 5 18 B2206668C 61001213 AA 6202 6203 Zoned Comfort Control Install EN...

Reviews: