USE TWO SCREWS WHEN 

ATTACHING TO A WALL STUD

USE FOUR SCREWS 

WHEN ATTACHING TO 

DRYWALL/PLASTER

ZONE CONTROL

ZONE CONTROL

1

2

90-2109

90-2110

FIGURE 4 

– MOUNTING HOLE LOCATIONS

FIGURE 3

LOCATE DAT 

SENSOR IN 

SHADED AREA. 

(SUPPLY DUCT)

ZONE CONTROL 

MOUNTED ON 

WALL OR STUD

ZONE CONTROL 

MOUNTED ON 

RETURN DUCT

90-2111

FIGURE 5 

– LOCATION RECOMMENDATIONS

INSTALLATION

MOUNTING

1. 

Separate the zone 
panel cover from the 
base. See 

FIGURE 3

.

2. 

Use the base as a 
template to drill 
mounting holes. 
See 

FIGURE 4

 for 

mounting hole 
locations.

3. 

Attach the base to an 
interior wall, stud or 
return duct. 

INSTALLATION LOCATION RECOMMENDATIONS

1. 

Mount the zone panel near the HVAC equipment. Locate the panel 
on an interior wall, stud or return duct. See 

FIGURE 5

2. 

Locate the Discharge Air Temperature (DAT) in the supply trunk, 
downstream of the heat exchanger and cooling coils, and before the 
zone dampers (refer to the shaded areas of 

FIGURE 5

). 

Note:

 Do 

not mount the sensor in direct line-of-sight of the heat exchanger, 
cooling coils or UV lights as this may cause the sensor to report false 
temperature readings. Do not route wires along 120VAC lines. 

3. 

Before wiring the sensor to the control panel, measure the resistance 
across the sensor. The resistance corresponds (approximately) to the 
sensed temperature according to the following table:

Temperature (°F)

30

40

50

60

70

80

90

100

Resistance (k )

34.6

26.1

19.9

15.3

11.9

9.4

7.4

5.9

5

B2206668C 61001213 AA 6202-6203 Zoned Comfort Control Install ENG-wrf.indd   5

6/14/18   3:28 PM

Summary of Contents for Zoned Comfort Control 6202

Page 1: ...READ AND SAVE THESE INSTRUCTIONS Model 6203 6202 Zoned Comfort Control Safety Installation Instructions B2206668C 61001213 AA 6202 6203 Zoned Comfort Control Install ENG wrf indd 1 6 14 18 3 28 PM...

Page 2: ...cooling system is properly sized and balanced 5 Insufficient air flow or excessive temperatures through the heating and cooling system could result in equipment damage Refer to the manufacturer s rec...

Page 3: ...IGURE 1 8 63 219 9 66 245 1 86 47 ZONE CONTROL 90 2108 FIGURE 1 ZONE PANEL DIMENSIONS IN INCHES mm APPLICATION ACCESSORIES APPLICATION The Model 6203 and 6202 Zone Panels are for conventional heat coo...

Page 4: ...12 COOLING Green Cooling is active Flashing DAT low temperature limit reached 13 FAN Green Fan output is active 14 ZONE 1 Green Damper is open Red Damper is closed 15 ZONE 2 Green Damper is open Red D...

Page 5: ...HVAC equipment Locate the panel on an interior wall stud or return duct See FIGURE 5 2 Locate the Discharge Air Temperature DAT in the supply trunk downstream of the heat exchanger and cooling coils...

Page 6: ...ly with applicable codes ordinances and regulations Use only 18 or 20 gauge solid non stranded wire Strip off 7 16 of insulation from the wire Push wire into the terminal of the zone panel To release...

Page 7: ...one panel and thermostats Example If you have a 3 zone system and there are two dampers per zone then the total number of dampers that could be energized at one time is 6 2 4 dampers 4 dampers x 10VA...

Page 8: ...ed damper For power open and power close dampers this terminal is used to power open the damper NO This terminal is used to power close a normally open damper For power open and power close dampers th...

Page 9: ...ermostat W Heating Y Cooling G Fan NOTE Heat cool thermostats must be used for all zones FURNACE AND A C HVAC TERMINAL DEFINITIONS Y1 First stage cooling W1 First stage heating G Fan BOILER AND A C HV...

Page 10: ...to the zone panel for heating the zone panel will initiate a heating call to the equipment and close the damper for all zones that are not calling for heat Following a 2 minute minimum on time the hea...

Page 11: ...OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED THIS LIMITED WARRANTY IS VOID IF DEFECTS S RESULT FROM FAILURE TO HAVE THIS UNIT INSTALLED BY A QUALIFIED HEATI...

Page 12: ...1467 Madison WI 53701 1467 800 334 6011 F 608 257 4357 2018 Aprilaire Division of Research Products Corporation 61001213 B2206668C 5 18 B2206668C 61001213 AA 6202 6203 Zoned Comfort Control Install EN...

Reviews: