![Aprilaire 8800 Programmer'S Manual Download Page 53](http://html.mh-extra.com/html/aprilaire/8800/8800_programmers-manual_2956180053.webp)
HOlDSTAT
Thermostat program hold status
COS: C17
Permissions: Read/Write
Query
Command
Syntax:
SN[#] HOLDSTAT?<CR>
Description: Requests the thermostat program hold status .
Assignment
Command
Syntax:
SN[#] HOLDSTAT=NONE<CR>
Description: Cancels all active holds . The assignment command has only this syntax .
Response or
COS Message
Syntax:
SN[#] HOLDSTAT=[value]<CR>
Example:
SN1 HOLDSTAT=NONE<CR>
Node address 1 responds with a hold status of NONE .
Parameters
Range
value:
hold status code
[NONE, TEMP, PERM, VAC]
NONE:
no holds are currently active
TEMP:
a temporary hold is active
PERM:
a permanent hold is active
VAC:
a vacation hold is active
The assignment command is only available for cancelling active holds . This command is ignored if the controller type is set to humidistat .
Holds can be changed (initiated or cancelled) through the thermostat Home Screens . If the hold status is changed at the thermostat, a C17
COS unsolicited message is issued (if C17 is ON) .
HOlD
Network override status
COS: C6
Permissions: Read/Write
Query
Command
Syntax:
SN[#] HOLD?<CR>
Description: Requests the network override status .
Assignment
Command
Syntax:
SN[#] HOLD=[value]<CR>
Description: Sets the network override status to
[value]
.
Response or
COS Message
Syntax:
SN[#] HOLD=[value]<CR>
Example:
SN1 HOLD=OFF<CR>
Node address 1 responds with a network override status of OFF .
Parameters
Range
value:
network override status
[OFF, ON]
This command is ignored if the NETLK network override lockout setting is set to enabled .
Network override status can be changed through the Home Screens . If the network override status is changed at the node, a C6 COS
unsolicited message is issued (if C6 is ON) .
53