VACHOlD
Vacation hold
COS: N/A
Permissions: Read/Write
Query
Command
Syntax:
SN[#] VACHOLD?<CR>
Description: Requests the configuration of the thermostat program vacation hold .
Assignment
Command
Syntax:
SN[#] VACHOLD=[mm][dd][yy] [hh][mm] [HT] [CL] [fan]<CR>
SN[#] VACHOLD=[mm][dd][yy] [hh][mm] [HT] [fan]<CR>
SN[#] VACHOLD=[mm][dd][yy] [hh][mm] [CL] [fan]<CR>
Description: Configures a vacation hold to end on
[mm][dd][yy]
at
[hh][mm]
with a heat setpoint of
[HT]
, a
cool setpoint of
[CL]
and fan mode of
[fan]
. If the thermostat is configured with a Control Setup of Heat
Only or Cool Only or if the system mode is set to Heat, Emergency Heat or Cool, only the respective setpoint is
used . The syntax with both setpoints is only used when the system mode is AUTO .
Example:
SN1 VACHOLD=011511 1200 62 AUTO<CR>
Response
Syntax:
SN[#] VACHOLD=[mm][dd][yy] [hh][mm] [HT][scale] [CL][scale] [fan]<CR>
SN[#] VACHOLD=[mm][dd][yy] [hh][mm] [HT][scale] [fan]<CR>
SN[#] VACHOLD=[mm][dd][yy] [hh][mm] [CL][scale] [fan]<CR>
Example:
SN1 VACHOLD=011011 1900 65F AUTO<CR>
Node address 1 responds with a vacation hold configured to end on January 10, 2011 at 7:00PM with a heat
setpoint of 65°F and fan mode of AUTO .
Parameters
Range
mm:
end date month
[01 – 12]
dd:
end date day
[01 – 31]
yy:
end date year
[00 – 99]
hh:
end time hours in 24-hour format
[00 – 23]
mm:
end time minutes
[00 – 59]
HT:
hold heat setpoint
Fahrenheit
[40 – 90]
Celsius
[4 – 32]
CL:
hold cool setpoint
Fahrenheit
[42 – 99]
Celsius
[6 – 37]
fan:
hold programmed fan mode
[AUTO, A, ON, CIRC]
AUTO, A:
fan auto mode
ON:
fan on mode
CIRC:
fan circulate mode
scale:
temperature scale
[F, C]
F:
Fahrenheit
C:
Celsius
If a query command is received and a vacation hold is not active, no response is sent . If an assignment command is received and another
hold type is currently active, the currently active hold is replaced by the vacation hold . The current hold status is read using the HOLDSTAT
command . A vacation hold is cancelled using the HOLDSTAT command .
This command is ignored if the controller type is set to humidistat or if the thermostat is configured as non-programmable . The vacation hold
configuration state can be changed through the Home Screens for thermostat control . If the vacation hold configuration is changed at the
thermostat, a C17 COS unsolicited message is issued (if C17 is ON) .