SC
Controlling thermostat cool setpoint
COS: C5
Permissions: Read/Write
Query
Command
Syntax:
SN[#] SC?<CR>
Description: Requests the controlling thermostat cool setpoint .
Assignment
Command
Syntax:
SN[#] SC=[value]<CR>
Description: Sets the controlling thermostat cool setpoint to
[value]
.
Example:
SN1 SC=78<CR>
Response or
COS Message
Syntax:
SN[#] SC=[value][scale]<CR>
Example:
SN1 SC=78F<CR>
Node address 1 responds with a controlling cool setpoint of 78°F .
Parameters
Range
value:
cool setpoint
Fahrenheit
[42 – 99]
Celsius
[6 – 37]
scale:
temperature scale
[F, C]
F:
Fahrenheit
C:
Celsius
The thermostat controlling cool setpoint corresponds to the active cool setpoint to which the thermostat is controlling the cooling equipment .
Assignment commands are ignored if the controller type is set to humidistat .
When the thermostat system mode is set to AUTO, the heat and cool setpoints are interdependent and must abide by the deadband . If an
assignment command is received with a cool setpoint value that causes a deadband violation, the heat setpoint is automatically decreased
to fulfill the deadband requirement . If the deadband requirement cannot be fulfilled by decreasing the heat setpoint, the command is ignored
and no response sent .
If an assignment command is received while the thermostat is running the program schedule, the thermostat automatically initiates a
temporary hold with an end time of the start time of the next scheduled event . If a hold is active at the time of the assignment command,
the hold setpoint is modified . In addition, if a hold is initiated as a result of the receipt of this command, a C17 COS unsolicited message is
issued (if C17 is ON) .
If a query or an assignment command is received and the thermostat program format is programmable (i .e . not non-programmable), and the
system mode is set to Heat, Emergency Heat or OFF, this command is ignored .
Integer values must be within the range specified for the current temperature scale . The cool setpoint can be changed through the Home
Screens for thermostat control or due to a schedule or hold change . If the cool setpoint is changed at the thermostat, a C5 COS unsolicited
message is issued (if C5 is ON) .
40