TEMPERATURE CONTROl COMMANDS
MODE, M
Control mode
COS: C7
Permissions: Read/Write
Query
Command
Syntax:
SN[#] MODE?<CR>
SN[#] M?<CR>
Description: Requests the control mode .
Assignment
Command
Syntax:
SN[#] MODE=[value]<CR>
SN[#] M=[value]<CR>
Description: Sets the control mode to
[value]
.
Examples:
SN1 MODE=HEAT<CR>
SN1 M=A<CR>
Response or
COS Message
Syntax:
SN[#] M=[value]<CR>
Description: The thermostat sends the control mode . The
[value]
parameter is always in the verbose format .
Example:
SN1 M=COOL<CR>
Node address 1 responds with a control mode of Cool .
Parameters
Range
value:
control mode
[OFF, O, HEAT, H, COOL, C, EMHT, E, AUTO, A, HUMID, DEHUM]
OFF, O:
Off mode – Thermostat or Humidistat
HEAT, H:
Heat mode – Thermostat
COOL, C:
Cool mode – Thermostat
EMHT, E:
Emergency heat mode (heat pump only) – Thermostat
AUTO, A:
Auto mode – Thermostat or Humidistat
HUMID:
Humidification – Humidistat
DEHUM:
Dehumidification – Humidistat
The control mode can be changed through the Home Screens for thermostat control or through the Setup Screens for humidity control . If the
control mode is changed at the node, a C7 COS unsolicited message is issued (if C7 is ON) .
36