![Aprilaire 8800 Programmer'S Manual Download Page 25](http://html.mh-extra.com/html/aprilaire/8800/8800_programmers-manual_2956180025.webp)
AlARM COMMANDS
flTAlMP
WPAlMP
DEHAlMP
SySAlMP
Air filter alarm period
Humidifier alarm period
Dehumidifier alarm period
HVAC system alarm period
COS: N/A
Permissions: Read/Write
Query
Command
Syntax:
SN[#] [alarm]ALMP?<CR>
Description: Requests the
[alarm]
alarm period setting .
Assignment
Command
Syntax:
SN[#] [alarm]ALMP=[value]<CR>
Description: Sets the
[alarm]
alarm period to
[value]
.
Examples:
SN1 FLTALMP=OFF<CR>
SN1 SYSALMP=12<CR>
Response
Syntax:
SN[#] [alarm]ALMP=[value]<CR>
Example:
SN1 FLTALMP=OFF<CR>
Node address 1 responds with an air filter alarm period setting of OFF .
Parameters
Range
alarm:
alarm command code
[FLT, WP, DEH, SYS]
value:
alarm period setting in months
FLT
[OFF, 1, 3, 6, 12]
WP, DEH, SYS
[OFF, 1 – 12]
Default: OFF
25