Working Standard
User’s Guide
WS-UGFW619-EN
www.appliedp.com
92
Request for measured samples of the waveform. Returns first 64 values from specific channel (phase
(0=L1, 1=L2, 2=L3), unit (0=U, 1=I)). Answer: amplitude samples (64 comma separated real
numbers).
MEAS:SIGN:AMPL? {<phase (0|1|2)>},{< unit (0|1)>}
Request for measured amplitude values of higher harmonic content. Returns first 40 values from
specific channel (phase (0=L1, 1=L2, 2=L3), unit (0=U, 1=I)). Answer: 40 comma separated real
numbers.
MEAS:SIGN:PHAS? {<phase (0|1|2)>},{< unit (0|1)>}
Request for measured phase shifts of higher harmonic content. Returns first 40 values from specific
channel
(phase (0=L1, 1=L2, 2=L3), unit (0=U, 1=I). Answer: phase shifts (40 comma separated
numbers).
MEAS:OPER {<param>}
Setting of Operation M
ode. Parameter is Operation Mode’s number (0-7) or code (P6-K3).
MEAS:OPER?
Request for setting of Operation Mode. Replay is Operation Mode’s number (0-7).
MEAS:CONN:TYP {<param>}
Connection setting. Parameters: 0 - 3P4W, 1 - 3P3W, 2 - 2P3W, 3 - 1P3W, 4 - 1P2W
MEAS:CONN:TYP?
Request for connection setting. Answers: 0 - 3P4W, 1 - 3P3W, 2 - 2P3W, 3 - 1P3W, 4 - 1P2W
MEAS:CHNLA:AC?
Request for values from Input A.
MEAS:CHNLA:AC:PHAS?
Request for values of phases from Input A.
MEAS:CHNLA:AC:SUM:SQ?
Request for sum of square voltages or currents from Input A.
MEAS:CHNLA:AC:DIST?
Request for distortion of measured voltage or current from Input A.
MEAS:CHNLA:MOD?
Request for accessories type connected to Input A.
Answer can be: 2 … voltage, 1 … current, 0 … none.
MEAS:CHNLB:AC?
Request for values from Input B.
MEAS:CHNLB:AC:PHAS?
Request for values of phases from Input B.
MEAS:CHNLB:AC:SUM:SQ?
Request for sum of square voltages or currents from Input B.
MEAS:CHNLB:AC:DIST?
Request for the distortion of measured voltage or current from Input B.