Working Standard
User’s Guide
www.appliedp.com
WS-UGFW619-EN
49
4.12.1 Measurement Settings
This page, divided to six screens, contains parameters of measurement mode.
Meas. Settings screen 1/6
* P12
Meas. Settings screen 2/6
* P13
Connect. type
......................... Connection type:
3P4W
,
3P3W
,
2P3W
,
1P3W
or
1P2W
(see
appendix Connection Diagrams). If parameter Start-up Mode is set to
Test, then this value is overwritten by value of currently selected
meter from database.
ENERGY OUTPUT
.................. Settings of energy (impulse) output in order to test the Working
Standard by another etalon. Impulse output is realized by frequency
generation of the red LED, and if AUX parameter is enabled, then
even by AUX output (included BNC cabled is connectable there).
State
............................ Type of measured energy:
Active
,
Reactive
or
Apparent
Energy or
Fixed frequency
Fixed freq.
................... Value of fixed frequency generated on red impulse LED or on
connected BNC cable if parameter State has value Fixed frequency
Factor
.......................... Constant of device which determines the relation between actually
measured power and frequency on Impulse output
Factor unit
................... Unit of parameter Factor:
i/kWh
,
i/Wh
,
i/Ws
,
i/kWs
,
kWh/i
,
Wh/i
,
Ws/i
,
kWs/i
,
MWh/i
or
i/MWh
AUX output
.................. Impulses in AUX output:
ON
(enabled) or
OFF
(disabled)
Channel LX
.................. channel enabling (X = 1 or 2 or 3) for energy output measurement:
ON
(enabled) or
OFF
(disabled)
FREQUENCY
.......................... Settings of frequency measurement
Freq. mode
.................. mode of frequency measurement:
Auto
when
Default freq. and Sync.
chnl. items are enabled; or
Fixed
when Fixed freq. item is enabled
Default freq.
................ Default measurement frequency:
50 Hz
or
60 Hz
Sync. chnl.
.................. Synchronization channel used for frequency measurement:
UL1
,
UL2
,
UL3
,
IL1
,
IL2
,
IL3
or
AUTO
Fixed freq.
...................
Frequency output doesn’t reflect currently measured power,
frequency output generates constant frequency