Working Standard
User’s Guide
WS-UGFW619-EN
www.appliedp.com
78
SYST:SET:COM2?
Request for actual settings of USB serial communication. See command SYST:SET:COM?
SYST:SET:COM2 {<baudrate (300-115200)>}
Setting parameters of USB serial communication. See command SYST:SET:COM?
SYST:CONF:SAV
Save configuration.
SYST:CONF:LOAD
Load user configuration.
SYST:CONF:LOAD:DEF
Load default configuration (from FW version 4.03).
SYST:UIC?
Request for the state of checking (voltage) unconnected input. Answer is:
0
– noise values enabled (measured values will be used in calculations)
1
– noise cancelation (zero values are used for further calculations)
SYST:UIC{<uic_val>}
Setting the state of checking unconnected input(s).
SYST:STAT?
Request for status of the device. Answer is:
-1
… (calibration or self-calibration is in progress), 1 … (standard measuring mode is active)
SYST:BATT?
Request for the battery status of the device. Reply is:
0 - 3
… different voltage level of batteries, 4 … battery charger connected.
Impulse Output
Device’s impulse output is used for continuous energy measurement. Frequency of impulses is a
product of measured absolute power value and the constant of frequency output. The impulse output
can be configured to generate a constant frequency as well.
The impulse output can be controlled by remote interface commands:
SYST:ENER:CHAN?
Request for the setting of the individual channel selection for functions related to the energy. Reply are
three (in a sequence for channels L1, L2 and L3) values 0 or 1 (0 denounce for switched-off and 1 for
switched-on given channel
selection, respectively) separated by a commas (e.g. “1,0,1”).
SYST:ENER:CHAN {OFF|ON},{OFF|ON},{OFF|ON}
Setting of the individual channel selection for functions related to the energy. The parameters value (in
a sequence for channels L1, L2 and L3) is ON or OFF for switched-on or switched-off given channel
selection, respectively. This setting influences the summing up of the individual channels into the value
of the generated frequency on the device impulse output if this is in the ENERGY mode.
SYST:ENER:ALG?
Request for the setting of method of summing energy. Possible answers are 0 = 4Quadrant, 1 = Algo1
(Net Result), 2 = Algo2 (Positive Aggregate), 3 = Algo3 (Both Sum), 4 = Algo4 (Anti-fraud).