Trip Condition
_0 - Near
Near
activates the trip status whenever the target surface is closer than the Trip Value setting.
Trip Condition
_1 - Exclusive
Exclusive
activates the trip status whenever the target
surface is closer than the Trip Value setting OR beyond
the Trip Value + Trip Window setting.
Trip Condition
_2 - Hysteresis Near
Hysteresis Near
activates the trip status whenever the
target surface moves closer than the Trip Value setting.
The trip status remains activated until the target surface
moves beyond the Trip Value + Trip Window setting. The
trip status remains off until the target surface moves
closer than the Trip Value setting again.
Trip Condition
_3 - Far
Far
activates the trip status whenever the target surface
is beyond the Trip Value setting.
Trip Condition
_4 - Inclusive
Inclusive
activates the trip status whenever the target
surface is beyond the Trip Value setting AND closer the
Trip Value + Trip Window setting.
Trip Condition
_5 - Hysteresis Far
Hysteresis Far
activates the trip status whenever the target surface moves beyond the Trip Value + Trip
Window setting. The trip status remains activated until the target surface moves closer than the Trip Value
setting. The trip status remains off until the target surface moves beyond the Trip Value + Trip Window
setting again.