APG Modbus software can be used in tandem with an APG RST-6001 Modbus Controller to program and
control up to 20 MNU IS sensors. Through the APG Modbus software, you can monitor the raw readings
from the sensor, or configure the sensor. See MNU IS Modbus Register Lists below.
•
Modbus Programming with APG Modbus Software
NOTE
: For APG Modbus programming instructions, or to download APG Modbus soft-
ware, please visit
www.apgsensors.com/support
.
•
MNU IS Modbus Register Lists
Input Registers (0x04)
Register
Returned Data
30299
Model Type
30300
Raw Distance/Level Reading (in mm, unsigned)
30301 N/A
30302
Temperature Reading (in
0
C, signed)
30303-30304
Calculated (raw)
30305-30306
N/A
30307 (upper byte)
Version
30307 (lower byte)
Signal Strength
30308 N/A
30309 (upper byte)
Trip 1 Alarm
30309 (lower byte)
Trip 1 Status
30310 (upper byte)
Trip 2 Alarm
30310 (lower byte)
Trip 2 Status
30314-30318
10 Byte Sensor Serial Number
30500-30598
Quickmode
Samples
NOTE
: The Calculated Readings will be returned without a decimal place. In order to
obtain the true result, the Decimal Place setting must be taken into account.