8
TC5-1N5FAB rev.06
To connect the controller, refer to the wiring diagram enclosed with this user's
manual.
n
Set the voltage switch to the appropriate voltage.
n
Use the electrical knockouts provided at the bottom of the enclosure.
Do not make additional holes in the enclosure, particularly on the side
of the enclosure when using a computer communications module.
n
It may be necessary to install a transformer in order to supply the
appropriate voltage to the heating unit.
ALARM CONNECTION:
There are two types of alarms on the market. One
type activates when current is cut off at its input, whereas the other activates
when current is supplied at its input. For an alarm of the first type, use the NO
terminal as shown on the wiring diagram. For an alarm of the second type, use
the NC terminal.
ALL WIRING MUST BE DONE BY AN AUTHORIZED ELECTRICIAN
AND MUST COMPLY WITH APPLICABLE CODES, LAWS AND
REGULATIONS. BE SURE POWER IS OFF BEFORE DOING ANY
WIRING TO AVOID ELECTRICAL SHOCKS AND EQUIPMENT DAM-
AGE.
INSTALLATION
M
OUNTING INSTRUCTIONS
C
ONNECTIONS
Open the latch and lift the cover. Remove the black caps located on each of
the four mounting holes. Mount the enclosure on the wall using four screws.
Be sure the electrical knockouts are at the bottom of the enclosure in order
to prevent water from entering the controller. Insert the screws in the mounting
holes and tighten. Fasten the four black caps provided with the controller onto
the four mounting holes. The enclosure must be mounted in a location that
will allow the cover to be completely opened right up against the wall.
!
WARNING
65
TC5-1N5FAB rev.06
TC5-1N5FAB
POSITION
DISPLAY
MEANING
STAGE 1 - MIN.
SPEED / CURVE
flashing value
User-adjusted minimum speed.
steady value
Minimum speed calculated using the minimum
speed curve.
On / OFF
Status of minimum speed curve
dAY
Day number of the curve point for minimum
speed
SPd
Minimum speed of the curve point for minimum
speed
Cur.dAY
The current day reference for minimum speed
curve.
STAGE 1 -
BANDWIDTH/
TIMER
flashing value
Bandwidth
Ou.C
Bandwidth displayed is compensated for
outside temperature
On
Time On for minimum ventilation cycle
OFF
Time off for minimum ventilation cycle
tYP
Motor type for variable speed motors
STAGE 1 -
HUMID ITY
steady value
C urrent relative humidity reading.
Lo / Hi
Minimum and maximum humidity levels.
On / OFF
Status of humidity compensation.
set rH
The relative humidity set point.
SPd
Minimum Speed Compensation.
On
Time on for Heater 1 timer.
OFF
Time off for Heater 1 timer.