20
TC5-1N5FAB rev.06
TC5-1N5FAB
1
Specifying the Curve
n
Set the selection knob to
SET
POINT / T
o
CURVE
. The current
temperature set point flashes
on the display.
n
Press the push-button. The word
OFF
is displayed indicating that the
termperature curve is deactivated. If this is not the case, see below to
deactivate the curve.
Repeat the following steps for each of the six points:
n
Press the push-button once again. The day number is displayed,
alternating with the word "
day
".
n
Using the adjustment knob, set the day number to the desired value.
n
Press the push-button once again. The current temperature set point
is displayed, alternating with the word "
set
".
n
Using the adjustment knob, adjust the set point to the desired value.
Once the six points of the curve have been specified, activate the curve as
explained below.
NOTE
: Make sure the temperature curve is deactivated before specifying
new points (see below).
53
TC5-1N5FAB rev.06
TC5-1N5FAB
2
Adjusting Max. Temperature Difference Between
Zones
When using zoned heating, a built-in protection will operate the fans accord-
ing to the probes of the zone with the highest temperature whenever the
temperature difference between zones is greater than this parameter. The
default value is 7.5°F (4.2°C) and values range from 5°F to 40.0°F (2.8°C to
22.2°C).
n
Set the selection knob to
HEAT 1- 2 — OFFSET/DIFF.
The current
heater 1 offset is displayed, alternating with the letters "
OFT
" and
"
Ht.1
".
n
Press the push-button four times. The maximum temperature differ-
ence between zones is displayed, alternating with the letters "
Zon
dif
".
n
Use the adjustment knob to adjust the temperature difference to the
desired value.