4.6 Transmission cable type and precautions
General-purpose cabtyre cables, twist pair cables and dedicated flat cables, etc., can be used for the
transmission cable.
Use the following for electric wires.
• General-purpose 2-wire/4-wire cable (VCTF, VCT 0.75 to 1.25 mm
2
, rated temperature 60
C)
• General-purpose electric wire (0.75 to 1.25 mm
2
, rated temperature 60
C)
• Dedicated flat cable (0.75 mm
2
, 1.25 mm
2
, rated temperature 70
C)
Shield cable
• Since AnyWire has high noise resistance, it is unnecessary to use a shield cable.
Note that an improperly grounded shield cable shielding may result in trouble at the time of use.
Transmission cable
• Be careful to prevent the voltage from lowering below the lower limit of the allowable voltage range due
to voltage drop by the cable.
Lowering below the lower limit may result in malfunction.
If the voltage drops significantly, install a local power supply.
• Do not connect soldered wire directly to a terminal. Looseness may result in contact failure.
CAUTION