3. Switch setting
3.1 MODE switch
A number of bits for the AnyWireASLINK system is specified by combinations of MODE switches 1, 2
and 3.
MODE switch
Number of bits
1
2
3
ON
ON
OFF
32 inputs, 32 outputs
OFF
ON
OFF
64 inputs, 64 outputs
ON
OFF
OFF
128 inputs, 128 outputs
OFF
OFF
OFF
256 inputs, 256 outputs
(Factory setting)
* Any setting other than those in the above table is not allowed.
EtherCAT process data size is specified by ON/OFF setting of MODE switch 4.
MODE switch
Mode
Process data size
4
OFF
Normal mode
IN: 1352 bytes, OUT: 1352 bytes
(Factory setting)
ON
Saving mode
IN: 200 bytes, OUT: 200 bytes
Before setting a number of bits and process data size, be sure to turn OFF the power supply.
3.2 SET switch
This switch is used to clear error flags and perform the automatic address recognition.
(1) Clearing error flags
Press the SET switch to clear error flags.
Operation of this
switch is the same as that of the “Error flag clear” command output.
P. 5-7
(2) Automatic address recognition
By keeping the switch pressed for about two seconds or longer, the SET LED lights up and the
automatic address recognition process starts.
P. 6-1