-L*A1AW  2/12-

ALM

LINK

IN

Example of mixture of two-wire (non-isolated) 

    and four-wire (isolated) terminals

ALM

LINK

IN

The branching has 
no limitation.

Black: DN

Red: DP

Black: 
DN

Red: DP

AnyWireASLINK
Master

24V DC*

Black: DN

Red: DP

Black: DN

Red: DP

Black: DN

Red: DP

Black: DN

Red: DP

Black: DN

Red: DP

BT0

Red: DP  Black: DN

ALM

LINK

IN

ALM

LINK

IN

ALM

LINK

IN

Black: DN

Red: DP

Black: DN

white

Green

Green

Red: DP

Two-point

Two-point

Photoelectric head

Photoelectric head 0
Photoelectric head 1
Photoelectric head 2

4-20mA

4-20mA

1-5V

Fiber head

ALM

LINK

IN

ALM

LINK

IN

4P link connector 

is convenient for 

branching.

The branching has 
no limitation.

Dedicated flat cable

1.25mm

2

 (four-wire)

Black: DN

Red: DP

Black: 
DN

Red: DP

AnyWireASLINK
Master

24V DC*

Black: DN

Red: DP

Black: DN

Red: DP

Black: DN

Red: DP

Red: DP  Black: DN

Black: DN

Red: DP

AnyWireASLINK terminator

One terminator should be connected to the DP, DN terminal 
farthest from the AnyWireASLINK master. 
Connect it correctly so as not to set the wrong polarity.

Black: DN

Red: DP

BT0

Red: DP  Black: DN

ALM

LINK

IN

ALM

LINK

IN

ALM

LINK

IN

ALM

LINK

IN

Black: DN

Red: DP

Black: DN

Red: DP

White: 0V

Green: 24V

Two-point

Two-point

Two-point

Two-point

Two-point

Eight-point

Eight-point

24V DC*

Photoelectric head

Photoelectric head 0
Photoelectric head 1
Photoelectric head 2
Photoelectric head 3

Fiber head

General-purpose power supply filter

ASLINK filter

××

×: Green and white are not used 

    for two-wire connection.

    Protect the terminals from contact with other wires.

4-20mA

4-20mA

1-5V

Relationship between the size and length of the transmission line 

    and the supply current (Table 1)

CAUTION

- Refer to Table 1 so that the size and length of the 

transmission line and the allowable supply current lie 

within an appropriate range.

- Connect the same symbols (DP, DN) correctly between the AnyWireASLINK 

master and each device.

- The branching length and branch number have no limitations.

- Include the length of the cable provided with the terminal in the "total line 

length."

- Connect the terminator "BT0 (polar)" to the terminal on the transmission line 

farthest from the AnyWireASLINK master.

Supply current on the transmission line (DP, DN)

Total length

50m or less

1.25mm

2

0.75mm

2

MAX 2A

MAX 1.2A

MAX 1A

MAX 0.6A

MAX 0.5A
MAX 0.3A

0.5mm

2

MAX 0.8A

MAX 0.4A

MAX 0.2A

Total length: Over 50m,

no longer than 100m

Size of 

the transmission 

line (DP, DN)

Total length: Over 100m,

no longer than 200m

[How to connect AnyWireASLINK]

Connection example using a two-wire (non-isolated) terminal

[Connection Example]

You can select use of either a two-wire or four-wire terminal for the AnyWireASLINK according 
to the load current.
This Products Guide describes a two-wire (non-isolated) terminal.
If the load current is small, using a two-wire (non-isolated) terminal allows for achieving 
simplified wiring without a local power supply.
If you are prioritizing the sites of concentrated loads or the number of units connected, 
hybridization with a four-wire (isolated) terminal, which supports local power supply, is also 
possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving using an 
external power supply.
In the case of hybridization, refer to the Four-Wire (Isolated) Terminal Products Guide 
separately.

2P link connector is 

convenient for 

branching.

General-purpose 

cabtire cable

Dedicated flat cable

1.25mm

2

 (two-wire)

AnyWireASLINK terminator

One terminator should be connected to the DP, DN terminal 
farthest from the AnyWireASLINK master. 
Connect it correctly so as not to set the wrong polarity.

Two-point

Two-point

Two-point

Two-point

Two-point

Two-point

Two-point

Two-point

Two-point

Two-point

Two-point

Two-point

* Make sure to use a 

2 4 V   D C   s t a b i l i z e d  
power supply for the 
power supply to be 
connected.

* When complying with the 

UL Standard, make sure 
to use a 24V DC stabilized 
power supply of "NEC 
Class 2 Output."

The sum of the     

portions of DP, DN is 

the total line length.

CAUTION

Make sure to use a four-wire (isolated) terminal if connecting 
to a load (e.g. input/output port) controlled by a different 
power supply than that used in the AnyWireASLINK.
Otherwise, a malfunction may occur.

General-purpose power supply filter

The sum of the     

portions of DP, DN is 

the total line length.

Summary of Contents for ASLINKAMP L-A1AW Series

Page 1: ...mpany shall not be liable for any damages consequential or incidental to a malfunction of the delivered product Repair at cost After the expiration of the warranty period any troubleshooting or repair...

Page 2: ...ator BT0 polar to the terminal on the transmission line farthest from the AnyWireASLINK master Supply current on the transmission line DP DN Total length 50m or less 1 25mm2 0 75mm2 MAX 2A MAX 1 2A MA...

Page 3: ...24V DC stabilized power supply Two wire terminal Four wire terminal 24V 0V 24V 0V PE AnyWireASLINK master General purpose power supply filter Use if necessary If any of the side by side lines of DP D...

Page 4: ...V 0V Four wire terminal A B 24V 0V 24V 0V PE Filter notation in the drawing General purpose power supply filter Use if necessary General purpose power supply filter Use if necessary LOAD LINE EAC 06 4...

Page 5: ...unit Refer to P6 Decide the maximum number of extended devices within the range meeting the conditions below Extension Base Example 1 Considering based on the limit of I O points LA A1AW Input 16 poi...

Page 6: ...it is not used Example of local power supply To LP4 WW 10P crimped transmission line link connector FK4 125 100 LP4 WR 10P DP DN 24V 0V Master unit Master unit A D Circuit A D Circuit Control circuit...

Page 7: ...DP DN of the terminal 2 Setting is required for all AnyWireASLINKs devices Open the protection cover of the set analog input unit and direct the address writer to the setting port of the unit as show...

Page 8: ...Ex During 12 mA conversion LINK V mA ALM LINK V mA ALM About 3 seconds Display example during operation L A1AW 8 12 Data Structure Before shipment 0 Reference point shift mode 14 15 Conversion data 1...

Page 9: ...he AnyWireASLINK system and turn on the power Re connect to the AnyWireASLINK system The ASLINKAMP maintains the address 255 default setting Set any address other than 255 The ASLINKAMP has an address...

Page 10: ...00 16200 0 Over the upper limit value 200 Under the lower limit value 0 Over the upper limit value 200 Under the lower limit value 16000 16200 0 Over the upper limit value 200 3 8mA 0 95V 0 2mA Under...

Page 11: ...5Vp p max 512 max IN 256 OUT 256 Up to 128 units Bus type Multi drop method T branch method Tree branch method Connection mode Transmission line disconnection transmission line short circuit transmiss...

Page 12: ...2 Address Anywire Corporation Contact by mail Contact info_e anywire jp Contact by website http www anywire jp Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Printed in Japan 2016 2017 U...

Reviews: