[Troubleshooting]
■
Input abnormality detection
Over the lower limit of
the input value
Display example when the analog port is opened and disconnected
■
Input abnormality
0-10V
0-5V
1-5V
0-20mA
4-20mA
: 0.00
□
(End is undefined)
: 0.00
□
(End is undefined)
: Lo _ _
: 0.00
□
(End is undefined)
: Lo _ _
Confirm the input value to use within the specifications range.
LINK
V
mA
ALM
LINK
V
mA
ALM
Over the upper limit of
the input value
LINK
V
mA
ALM
LINK
V
mA
ALM
Repetition
Repetition
:
:
:
:
LINK
V
mA
ALM
■
Unit voltage (DP-DN) drop detection
LINK
V
mA
ALM
0.6 seconds
The display is the same for both the base unit and the extension unit.
7-segment display
ALM OFF
In the case of 1-5V, 4-20 mA setting:
Digital data -200 (FF38Hex.)
ALM OFF
Digital data: 16200 (3F48Hex.)
-L*A1AW 9/12-
[Monitor display]
LED display
LINK
V
mA
ALM
7-segment display
LINK
LINK
ALM
Name Indication status
ALM
Details
Normal
Slave unit voltage drop
Transmission error
DPDN disconnection, no power supply
Normal
The master unit detects
"ID duplication or non-setting" of this unit.
At the time of voltage input setting
At the time of current input setting
Flashing
Flashing
Alternate flashing
On
Off
Off
On
On
LINK
ALM
Normal status: LINK Flashing, ALM OFF, V/mA OFF
V
mA
Displays the operation status of this product using the
LEDs.
The display part is common in both the base unit and
extension unit.
A message of an input analog value, input abnormality, transmission
signal voltage drop and reference point shift mode operation is
displayed in the 7-segment display part.
LED Display
LINK
ALM
Cause
Measures
○
○
Off
Off
●
On
○
Off
◎
Flashing
(0.5 seconds
alternately)
◎
Flashing
(0.5 seconds
alternately)
-
◎
Flashing
(On for
0.2 seconds,
off for
1.0 seconds)
- AnyWireASLINK
transmission signal
is not connected.
- Power supply for
the AnyWireASLINK
system itself is not
turned on.
- The DP-DN line is
directly connected to
24-0V power supply.
- Confirm that there is no disconnection
between the ASLINKAMP and the
AnyWireASLINK system, and recover
the connection.
- Confirm the power status of the
AnyWireASLINK system, and turn on
the power.
- Re-connect to the AnyWireASLINK
system.
- The ASLINKAMP
maintains the
address 255
(default setting).
- Set any address other than 255.
- The ASLINKAMP has
an address redundant
with another unit.
- Look for the other unit which has the
same error indication, and set any
address different from it.
- The internal power
voltage of the
ASLINKAMP has
been reduced.
- Decrease the number of units
connected to the same
AnyWireASLINK system.
- Shorten the transmission line between
the ASLINKAMP and the master unit.
When the following errors are indicated on the display window of this
product, take measures as shown below.
Confirm whether analog output is connected or whether there is
disconnection, etc.
Confirm the input value to use within the specifications range.
Confirm the following issues to eliminate corresponding factors.
- Is the voltage of the 24 DC power supplied to the AnyWireASLINK master is
within the allowable voltage range?
- Is there any looseness or contact failure at the connection part of the main
line or branch line?
- Does the current of the unit or connection load suit system conditions?
Take measures as follows in the following case.
Symptom
Measures
Detection cannot be
performed.
Setting cannot be
performed with
ARW-04 and
ARW-03.
Indication
Cause
Measures
[E-0303]
The set parameter is
incorrect.
Check the parameter correspondence table and set
the correct parameter.
- Is wiring correct?
→
Re-confirm the analog port and the connection of the transmission line.
- Is power fed to the AnyWireASLINK system?
→
Confirm the power supply.
- Has address setting been performed?
→
Perform address setting.
- Are you using within the rated input range?
→
Use within the rated detection range.
- Is wiring correct?
→
Reconfirm the transmission line connection, and that the transmission signal is
applied.
- Is power fed to the AnyWireASLINK system?
→
Confirm the power supply.
- Was setting performed with the protective cover open?
→
Open the protective cover. Setting cannot be performed with the cover closed.
- Is the set parameter correct?
→
Check the parameter correspondence table and set the correct parameter.
When the following errors are indicated on ARW-04, take measures as
shown below.