[Troubleshooting]

Input abnormality detection

Over the lower limit of 
the input value

Display example when the analog port is opened and disconnected

Input abnormality

0-10V
0-5V
1-5V
0-20mA
4-20mA

: 0.00

 (End is undefined)

: 0.00

 (End is undefined) 

: Lo _ _ 
: 0.00

 (End is undefined) 

: Lo _ _

Confirm the input value to use within the specifications range.

LINK

V

mA

ALM

LINK

V

mA

ALM

Over the upper limit of 
the input value

LINK

V

mA

ALM

LINK

V

mA

ALM

Repetition

Repetition

LINK

V

mA

ALM

Unit voltage (DP-DN) drop detection

LINK

V

mA

ALM

0.6 seconds

The display is the same for both the base unit and the extension unit.

7-segment display

ALM OFF
In the case of 1-5V, 4-20 mA setting:
Digital data -200 (FF38Hex.)

ALM OFF
Digital data: 16200 (3F48Hex.)

-L*A1AW  9/12-

[Monitor display]

LED display

LINK

V

mA

ALM

7-segment display

LINK

LINK

ALM

Name Indication status

ALM

Details

Normal

Slave unit voltage drop

Transmission error

DPDN disconnection, no power supply

Normal

The master unit detects 

"ID duplication or non-setting" of this unit.

At the time of voltage input setting

At the time of current input setting

Flashing

Flashing

Alternate flashing

On

Off

Off

On

On

LINK
ALM

Normal status: LINK Flashing, ALM OFF, V/mA OFF

V

mA

Displays the operation status of this product using the 

LEDs.

The display part is common in both the base unit and 

extension unit.

A message of an input analog value, input abnormality, transmission 

signal voltage drop and reference point shift mode operation is 

displayed in the 7-segment display part.

LED Display

LINK

ALM

Cause

Measures

Off

Off

On

Off

Flashing

(0.5 seconds 
alternately)

Flashing

(0.5 seconds 
alternately)

Flashing

(On for 

0.2 seconds,

off for 

1.0 seconds)

- AnyWireASLINK 

transmission signal 

is not connected.

- Power supply for 

the AnyWireASLINK 

system itself is not 

turned on.

- The DP-DN line is 

directly connected to 

24-0V power supply.

- Confirm that there is no disconnection 

between the ASLINKAMP and the 

AnyWireASLINK system, and recover 

the connection.

- Confirm the power status of the 

AnyWireASLINK system, and turn on 

the power.

- Re-connect to the AnyWireASLINK 

system.

- The ASLINKAMP 

maintains the 

address 255 

(default setting).

- Set any address other than 255.

- The ASLINKAMP has 

an address redundant 

with another unit.

- Look for the other unit which has the 

same error indication, and set any 

address different from it.

- The internal power 

voltage of the 

ASLINKAMP has 

been reduced.

- Decrease the number of units 

connected to the same 

AnyWireASLINK system.

- Shorten the transmission line between 

the ASLINKAMP and the master unit.

When the following errors are indicated on the display window of this 

product, take measures as shown below.

Confirm whether analog output is connected or whether there is 
disconnection, etc.  
Confirm the input value to use within the specifications range.

Confirm the following issues to eliminate corresponding factors.
- Is the voltage of the 24 DC power supplied to the AnyWireASLINK master is 

within the allowable voltage range?

- Is there any looseness or contact failure at the connection part of the main 

line or branch line?

- Does the current of the unit or connection load suit system conditions?

Take measures as follows in the following case.

Symptom

Measures

Detection cannot be 
performed.

 

Setting cannot be 
performed with 
ARW-04 and 
ARW-03.

 

 

 

 

 

 

 

Indication

Cause

Measures

[E-0303]

The set parameter is 

incorrect.

Check the parameter correspondence table and set 

the correct parameter.

- Is wiring correct?
   

 Re-confirm the analog port and the connection of the transmission line.

- Is power fed to the AnyWireASLINK system?
   

 Confirm the power supply.

- Has address setting been performed?
   

 Perform address setting.

- Are you using within the rated input range?
   

 Use within the rated detection range.

- Is wiring correct?
   

 Reconfirm the transmission line connection, and that the transmission signal is 

applied.

- Is power fed to the AnyWireASLINK system?
   

 Confirm the power supply.

- Was setting performed with the protective cover open?
   

 Open the protective cover. Setting cannot be performed with the cover closed.

- Is the set parameter correct?
   

 Check the parameter correspondence table and set the correct parameter.

When the following errors are indicated on ARW-04, take measures as 
shown below.

Summary of Contents for ASLINKAMP L-A1AW Series

Page 1: ...mpany shall not be liable for any damages consequential or incidental to a malfunction of the delivered product Repair at cost After the expiration of the warranty period any troubleshooting or repair...

Page 2: ...ator BT0 polar to the terminal on the transmission line farthest from the AnyWireASLINK master Supply current on the transmission line DP DN Total length 50m or less 1 25mm2 0 75mm2 MAX 2A MAX 1 2A MA...

Page 3: ...24V DC stabilized power supply Two wire terminal Four wire terminal 24V 0V 24V 0V PE AnyWireASLINK master General purpose power supply filter Use if necessary If any of the side by side lines of DP D...

Page 4: ...V 0V Four wire terminal A B 24V 0V 24V 0V PE Filter notation in the drawing General purpose power supply filter Use if necessary General purpose power supply filter Use if necessary LOAD LINE EAC 06 4...

Page 5: ...unit Refer to P6 Decide the maximum number of extended devices within the range meeting the conditions below Extension Base Example 1 Considering based on the limit of I O points LA A1AW Input 16 poi...

Page 6: ...it is not used Example of local power supply To LP4 WW 10P crimped transmission line link connector FK4 125 100 LP4 WR 10P DP DN 24V 0V Master unit Master unit A D Circuit A D Circuit Control circuit...

Page 7: ...DP DN of the terminal 2 Setting is required for all AnyWireASLINKs devices Open the protection cover of the set analog input unit and direct the address writer to the setting port of the unit as show...

Page 8: ...Ex During 12 mA conversion LINK V mA ALM LINK V mA ALM About 3 seconds Display example during operation L A1AW 8 12 Data Structure Before shipment 0 Reference point shift mode 14 15 Conversion data 1...

Page 9: ...he AnyWireASLINK system and turn on the power Re connect to the AnyWireASLINK system The ASLINKAMP maintains the address 255 default setting Set any address other than 255 The ASLINKAMP has an address...

Page 10: ...00 16200 0 Over the upper limit value 200 Under the lower limit value 0 Over the upper limit value 200 Under the lower limit value 16000 16200 0 Over the upper limit value 200 3 8mA 0 95V 0 2mA Under...

Page 11: ...5Vp p max 512 max IN 256 OUT 256 Up to 128 units Bus type Multi drop method T branch method Tree branch method Connection mode Transmission line disconnection transmission line short circuit transmiss...

Page 12: ...2 Address Anywire Corporation Contact by mail Contact info_e anywire jp Contact by website http www anywire jp Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Printed in Japan 2016 2017 U...

Reviews: