[Notes on Combined Use with Four-Wire (Isolated) Terminals]

Insert the "ASLINK filter [Type ANF-01]" regardless of installation 
method and distance when complying with CE Standard.

If any of the side-by-side lines of DP, DN, 24V, or 0V exceeds the total length of 
50m in a power supply system to be supplied, serially connect the "ASLINK filter 
[Type ANF-01]" or "filter of COSEL Co., Ltd. [Type EAC-06-472]" to 24V and 0V in 
the starting position of the side-by-side lines.
This will improve noise resistance, reduce the impact of crosstalk by transmission 
signals, and stabilize the signals.
Insert a filter whether using a master power supply for the entire system or using a 
local power supply.

ASLINK filter

ANF-01

MAX 5A/24V DC

Filter of COSEL Co., Ltd.

EAC-06-472

MAX 6A/24V DC

Model

Type

Allowable power current

Filter allowable power current

AnyWire Type: ANF-01 Connection example

Power supply to the entire system

DP

DN

24V
0V

POWER IN

SLAVE

LG

24V

0V

L N FG

DP

DN

DP

DN

24V

0V

DP

DN

BT0

ANF-01

24V DC

stabilized 

power supply

Two-wire 

terminal

Four-wire 

terminal

24V

0V

24V

0V

PE

AnyWireASLINK master

General-purpose

power supply filter

(Use if necessary)

If any of the side-by-side lines 
of DP, DN, 24V, or 0V exceeds 
the total length of 50m

Local power supply/branching

POWER IN

SLAVE

DP

DN

24V
0V

LG

24V

0V

L N FG

DP

DN

24V

0V

DP

DN

DP

DN

24V

0V

DP

DN

BT0

ANF-01

24V DC

stabilized 

power 

supply

Two-wire 

terminal

DP

DN

Two-wire 

terminal

DP

DN

Two-wire 

terminal

Four-wire 

terminal

DP

DN

24V

0V

Four-wire 

terminal

Four-wire 

terminal

DP

DN

24V

0V

Four-wire 

terminal

DP

DN

24V

0V

Four-wire 

terminal

24V

0V

24V

0V

PE

AnyWireASLINK master

24V

0V

L

N

FG

24V DC

stabilized 

power supply

ANF-01

24V

0V

24V

0V

PE

DP

DN

24V

0V

Four-wire 

terminal

DP

DN

24V

0V

Four-wire 

terminal

A

B

ANF-01

For details of ANF-01, 
refer to ANF-01 Products Guide.

24V

0V

24V

0V

PE

Filter notation in the drawing

General-purpose 

power supply filter

(Use if necessary)

General-purpose 
power supply filter
(Use if necessary)

POWER IN

SLAVE

POWER IN

SLAVE

If (A+B) of the side-by-side 
lines of DP, DN, 24V, or 0V 
exceeds the total length of 50m

If any of the side-by-side lines 
of DP, DN, 24V, or 0V exceeds 
the total length of 50m

Summary of Contents for ASLINKAMP L-A1AW Series

Page 1: ...mpany shall not be liable for any damages consequential or incidental to a malfunction of the delivered product Repair at cost After the expiration of the warranty period any troubleshooting or repair...

Page 2: ...ator BT0 polar to the terminal on the transmission line farthest from the AnyWireASLINK master Supply current on the transmission line DP DN Total length 50m or less 1 25mm2 0 75mm2 MAX 2A MAX 1 2A MA...

Page 3: ...24V DC stabilized power supply Two wire terminal Four wire terminal 24V 0V 24V 0V PE AnyWireASLINK master General purpose power supply filter Use if necessary If any of the side by side lines of DP D...

Page 4: ...V 0V Four wire terminal A B 24V 0V 24V 0V PE Filter notation in the drawing General purpose power supply filter Use if necessary General purpose power supply filter Use if necessary LOAD LINE EAC 06 4...

Page 5: ...unit Refer to P6 Decide the maximum number of extended devices within the range meeting the conditions below Extension Base Example 1 Considering based on the limit of I O points LA A1AW Input 16 poi...

Page 6: ...it is not used Example of local power supply To LP4 WW 10P crimped transmission line link connector FK4 125 100 LP4 WR 10P DP DN 24V 0V Master unit Master unit A D Circuit A D Circuit Control circuit...

Page 7: ...DP DN of the terminal 2 Setting is required for all AnyWireASLINKs devices Open the protection cover of the set analog input unit and direct the address writer to the setting port of the unit as show...

Page 8: ...Ex During 12 mA conversion LINK V mA ALM LINK V mA ALM About 3 seconds Display example during operation L A1AW 8 12 Data Structure Before shipment 0 Reference point shift mode 14 15 Conversion data 1...

Page 9: ...he AnyWireASLINK system and turn on the power Re connect to the AnyWireASLINK system The ASLINKAMP maintains the address 255 default setting Set any address other than 255 The ASLINKAMP has an address...

Page 10: ...00 16200 0 Over the upper limit value 200 Under the lower limit value 0 Over the upper limit value 200 Under the lower limit value 16000 16200 0 Over the upper limit value 200 3 8mA 0 95V 0 2mA Under...

Page 11: ...5Vp p max 512 max IN 256 OUT 256 Up to 128 units Bus type Multi drop method T branch method Tree branch method Connection mode Transmission line disconnection transmission line short circuit transmiss...

Page 12: ...2 Address Anywire Corporation Contact by mail Contact info_e anywire jp Contact by website http www anywire jp Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Printed in Japan 2016 2017 U...

Reviews: