163
Doc.Id. HMSI-27-212
Anybus CompactCom 40 EtherNet/IP
Doc.Rev. 1.5
9 Enable communi-
cation settings
from Net
Get
BOOL
True
Value:Meaning:
True Can be set from network
False Cannot be set from network
See also...
- “TCP/IP Interface Object (F5h)” on page
87 (CIP-object)
- “Ethernet Link Object (F6h)” on page 90
(CIP-object)
- “Network Configuration Object (04h)” on
page 99
(Anybus Module Object)
11 Enable CIP for-
warding
Get
BOOL
False
Value:Meaning:
True Requests to unknown CIP objects
and unknown assembly object instances are
routed to the application.
False Requests to unknown CIP objects
and unknown assembly object instances are
not routed to the application.
See also...
- “Command Details: Process_CIP_Ob-
12 Enable Parame-
ter Object
Get
BOOL
True
Value:Meaning:
True Enable CIP Parameter Object
False Disable CIP Parameter Object
13 Input-Only heart-
beat instance
number
Get
UINT16
0003h
See also...
- “Instance 03h Attributes (Heartbeat,
Input-Only)” on page 67 (CIP-instance)
14 Listen-Only heart-
beat instance
number
Get
UINT16
0004h
See also...
- “Instance 04h Attributes (Heartbeat, Lis-
ten-Only)” on page 68 (CIP-instance)
15 Assembly object
Configuration
instance number
Get
UINT16
0005h
See also...
- “Instance 05h Attributes (Configuration
Data)” on page 68 (CIP-instance)
16 Disable Strict IO
Match
Get
BOOL
False
If true, the module will accept Class1 con-
nection requests that have sizes that’s less
than or equal to the configured IO sizes.
17 Enable uncon-
nected routing
Get
BOOL
False
If true, the module enables unconnected CIP
routing. This also triggers an initial upload of
the contents of the CIP Port Mapping object.
18 Input-Only
extended heart-
beat instance
number
Get
UINT16
0006h
See also...
- “Instance 06h Attributes (Heartbeat,
Input-Only Extended)” on page 68 (CIP-
instance)
19 Listen-Only
extended heart-
beat instance
number
Get
UINT16
0007h
See also...
- “Instance 07h Attributes (Heartbeat, Lis-
ten-Only Extended)” on page 69 (CIP-
instance)
20 Interface label
port 1
Get
Array of CHAR Port 1
The value of this attribute is used to change
the interface label for Ethernet Link Object
Instance #1
21 Interface label
port 2
Get
Array of CHAR Port 2
The value of this attribute is used to change
the interface label for Ethernet Link Object
Instance #2
22 Interface label
internal port
Get
Array of CHAR Internal
The value of this attribute is used to change
the interface label for Ethernet Link Object
Instance #3
# Name
Access Type
Default Value
Comment