SECTION 6 – TESTING AND PLACING IN SERVICE
UL EX3470 ULC EX3470
PAGE 6-4 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual
TESTING DETECTION SYSTEM (Continued)
i. Install cover on regulated release assembly and each
regulated actuator assembly and secure with appropriate
fasteners or visual inspection seal. Insert seal (Part No.
197) in each upper and lower cover hole, if applicable. If
system is installed in an OEM enclosure, attach enclosure
cover and secure with appropriate hardware or procedure.
CAUTION
Before installing cover, make certain detection tension
lever is secured in the “DOWN” position to enable
automatic detection and operation of the AUTOMAN
Regulated Release.
j. Record installation date on tag attached to unit and/or in a
permanent file.