SECTION 5 – INSTALLATION INSTRUCTIONS
UL EX3470 ULC EX3470
PAGE 5-26 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual
INSTALLATION OF REMOTE MANUAL PULL STATION OR
MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT
(Continued)
Connecting Flexible Conduit to Pulley Elbows, Pulley
Tees, or Union Fittings (Continued)
7. Slide the flexible conduit into the strain relief until it is
approximately 1/16 in. (1.6 mm) from the bottom of the flex-
ible conduit insert. See Figure 5-68.
SLIDE FLEXIBLE CONDUIT
APPROXIMATELY 1/16 IN.
(1.6 mm) FROM BOTTOM OF
FLEXIBLE CONDUIT INSERT
FIGURE 5-68
008001
8. Tighten the strain relief nut onto the strain relief. See Figure
5-69.
TIGHTEN STRAIN
RELIEF NUT
FIGURE 5-69
008002
9. Complete the same procedures on the other end of the
conduit fitting as described in Steps 1 through Step 8 above.
Assembling the Block
Note: For installations that do not require the tee block,
refer to page 5-34 for instructions.
1. The flexible conduit and wire rope should be connected to
the electrical box as described in “Connecting the Flexible
Conduit to the AUTOMAN Release, Electrical Box, or
Mechanical Gas Valve.” See Figure 5-70.
Note: For 1 1/2 in. (38 mm) deep electrical box, the bearing
should be installed in the block’s shallow box location.
For 2 1/8 in. (54 mm) deep electrical box, the bearing should
be installed in the block’s deep box location.
FIGURE 5-70
008003
2. Thread the wire rope through the small end of the block into
the bearing area to be used. See Figure 5-71.
SMALL END
OF BLOCK
FIGURE 5-71
008004
3. Pull slack, make a loop and insert the rope through the
larger opening in the bearing area. See Figure 5-72.
PUSH WIRE
ROPE THROUGH
LARGER
OPENING
FIGURE 5-72
008005