ALARM INITIATING SWITCH
The Alarm Initiating Switch Kit (Part No. 428311) can be field
mounted within the AUTOMAN release. This switch must be
used to close a supervised alarm circuit to the building main fire
alarm panel when the AUTOMAN release actuates. This action
will signal the fire alarm panel that there was a system actua-
tion in the kitchen area. The switch kit contains all necessary
mounting components along with a mounting instruction sheet.
The switch is rated 50 mA, 28 VDC.
FIGURE 3-31
004890
REGULATOR TEST KIT
The Test Kit Assembly (Shipping Part No. 56972) is required
to test the regulator setting and nitrogen flow during 12-year
maintenance examinations. This will ensure that the regulator
is functioning properly.
FIGURE 3-32
000169
VENT PLUG ASSEMBLY
The Vent Plug Assembly (Part No. 74274) is installed on the
agent tank adaptor to prevent pressure buildup within the agent
tank or distribution lines due to temperature fluctuations.
CARTRIDGE RECEIVER GASKET
The Cartridge Receiver Gasket (Part No. 181) is installed in the
release and actuator assembly cartridge receiver to create a
seal between the cartridge receiver assembly and the cartridge.
FUSIBLE LINK
Select correct UL Listed fusible link(s) for installation in detec-
tor(s) according to the temperature condition chart below:
SL STYLE
To Be Used
Fusible Link
Where
Shipping
Temperature Color
Assembly
Temperature
Does Not
of
Part No.
Rating
Exceed
Link
439085 (25) 165 °F
100 °F
Black
(74 °C)
(38 °C)
439086 (25) 212 °F
150 °F
White
(100 °C)
(66 °C)
439087 (25) 280 °F
225 °F
Blue
(138 °C)
(107 °C)
439088 (25) 360 °F
290 °F
Red
(182 °C)
(143 °C)
439089 (25) 450 °F
360 °F
Green
(232 °C)
(182 °C)
A-PC STYLE
Fusible Link
To Be Used
Shipping
Where
Assembly Temperature Temperature
Part No.
Rating
Does Not Exceed
439227 (10)
165 °F (74 °C)
100 °F (38 °C)
439228 (10)
212 °F (100 °C)
150 °F (66 °C)
439229 (10)
280 °F (138 °C)
225 °F (107 °C)
439230 (10)
360 °F (182 °C)
290 °F (143 °C)
439231 (10)
450 °F (232 °C)
360 °F (182 °C)
439232 (25)
500 °F (260 °C)
400 °F (204 °C)
SL STYLE
A-PC STYLE
000170
000171
FIGURE 3-33
MAXIMUM REGISTERING THERMOMETER
The Maximum Registering Thermometer (Part No. 15240) may
be used to indicate the highest normal temperature for the pro-
tected area. Once this is established, the correct rated fusible
link can be chosen. Other methods for determining maximum
temperatures may be used.
HOSE/GROMMET PACKAGE
The Hose/Grommet Package (Part No. 418511) consists of a
24 in. rubber hose and two grommets. This package is required
when expellant gas hose is routed outside the AUTOMAN
Regulated Release, Regulated Actuator, and/or tank enclosure
assemblies.
SECTION 3 – SYSTEM COMPONENTS
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 3-11
R-102 Restaurant Fire Suppression Manual
TEMPERATURE
RATING STAMPED ON
FUSIBLE LINK BODY
ALARM
INITIATING
SWITCH
SWITCH
COVER
SWITCH MOUNTING
BRACKET (NOT INCLUDED
WITH ALARM INITIATING
SWITCH KIT)
Summary of Contents for R-102