Condition:
Error code 57: Flame Rod
Shorted to Ground
Disconnect power. Shut off gas
supply to water heater. Slide out
burner assembly
(see section on
“removing pilot and main burner
assembly”).
Check to see if pilot shield is
touching pilot flame sensor or
flame sensor touching pilot hood.
Bend shield to prevent interference
or replace pilot shield.
Check pilot flame sense wire for
broken insulation. Replace pilot if
defective
Reinstall pilot and burner
assembly. Reconnect gas line
union, turn on gas.
Check for Gas Leaks
Reconnect power and verify
proper ignitions.
10.6.2 Pilot inspection
Make sure pilot shield
clears flame sense rod
Flame
sense
rod
Spark
Electrode
Fig. 86