Issue 2 14/07/16
85
Appendix 10
10.4.5 To display flame sense current of the pilot
flame sensor
The pilot flame sense current is available only when the burners
are in operation. Step 1: Make sure the status displays “Heating”
or draw enough hot water to start the burners. Step 2: Enter the
“Service Mode” described previously. Step 3: Press the “Select”
button until a number value is displayed with “Flame Current” to
the right of the number. The value displayed is in microamps
(μA).
10.4.6 To display and change temperature setpoint
Step 1: In “Service Mode” press the “Select” button until
“Setpoint” is shown in the water heater display
Step 2: Press the “Set” button to enter the setting mode.
“Setpoint” will flash in the water heater display.
Step 3: To raise the temperature setpoint, press the
“Temperature Up” button until the desired temperature
is shown on the water heater display.
Fig. 62
Fig. 63
Fig. 64
Fig. 65
Note
The maximum temperature that can be set in the Water
Heater Display is limited to the “Max Setpoint” described
previously. To change the “Max Setpoint”, refer to the
procedure “To Change the Maximum Setpoint Limit..."
described previously under “Accessing the Service Mode
on the Water Heater Display”.
Warning
Setting the water temperature to the maximum set point
can result in scalding hot water delivered to the taps. It
is highly recommended that the maximum setpoint be
adjusted to the lowest temperature possible for the
needs of the installation. Make sure the water heater
control display is not in a public area that can result in
the temperature settings being improperly adjusted.
“Setpoint” flashes
“Setpoint” flashes