Call in verify;
this menu allows access via a password to select between EN and Non-EN modes of system
operation for fault monitoring of device communication loss. In EN mode a fault due to the loss of
communication with a wireless linked component is indicated at the control and indicating equipment
within 300 seconds of occurrence of the fault. In Non-EN mode a fault due to the loss of communication
with a wireless linked component is indicated at the control and indicating equipment with 900 seconds
of occurrence of the fault. The default for each system is to EN mode.
Front Display
Advanced Call In Verify
Analogue Value 35 Mode;
this menu allows an analogue value 35 message from a detector, which is a
head dirty/ compensation fault to be a selectable option for displaying on the system. The reporting of
this status does not compromise the performance of the sensor and or the sensitivity. It is not
arequirement for detectors to report contamination events hence this selectable mode. The default is to
OFF which will not display these status message types.
Front Display
Advanced Analogue Value 35 Mode
Audio Detect;
this menu allows the No Sndr Audio fault reporting to be selectable between On and Off on
the interface and the Control Panel. If On is selected the Analogue value 1 which is the No Sndr Audio fault
description will be displayed on the interface and the Control Panel if this fault type occurs on a sounder
device. If Off is selected the above fault will not be displayed on the loop module or the Control Panel. The
default is set to Off as there are no requirements to display this message type.
Front Display
Advanced Audio Detect
Batt Smoothing;
this menu allows the Battery Low fault reporting to be selectable so verification of the
low battery can be ascertained before the fault Analogue Value 7 Fault type is displayed on the loop
module and the Control Panel. Available smoothing options are selectable between OFF = No smoothing
and 1-5 days smoothing in one day steps. If this feature is implemented the systems performance is not
compromised and the 30 day battery low warning is still achieved. The default is set to OFF so no
smoothing is implemented and the fault type is displayed instantly.
Front Display
Advanced Batt Smooth