Global Batt Stat;
this menu allows the wireless devices battery statuses to be viewed. The devices are
listed in loop and address order.
Each device will show the status of its two battery packs. The battery status information is displayed as
follows;
P1 and a full battery icon;
this indicates a good battery voltage is present in Pack 1.
P1 and a half full battery icon;
this indicates the battery voltage is low in Pack 1 and is a 30 day warning
indication.
P1 and an empty battery icon;
this indicates the battery voltage is low in Pack 1 and is a 7 day warning
indication.
P1 and an X symbol;
this indicates a battery from Pack 1 is missing.
P2 and a full battery icon;
this indicates a good battery voltage is present in Pack 2.
P2 and a half full battery icon
–
this indicates the battery voltage is low in Pack 2 and is a 30 day warning
indication.
P2 and an empty battery icon;
this indicates the battery voltage is low in Pack 2 and is a 7 day warning
indication.
P2 and an X symbol;
this indicates a battery from Pack 2 is missing.
Front Display
Advanced Global Batt Stat
Global Sig Stat; this menu will display the signal level in dB for each device and RCC over a 24 hour
period. This is listed in Loop and Address Number order. After the system has been running for a 24 hour
period the wireless device and RCC signal levels should display 20dB or above. If any devices are under
the signal level requirements, check the flowchart On How to Improve Device Signal Levels section for
guidance.
Front Display
Advanced Global Sig Stat
Meeting the acceptable signal levels shown ensures the immunity to site attenuation (path loss) is met.
Individual Test;
in this menu, output tests can be performed on individual devices. This will allow the
LED
’
s to be turned on for detectors and call points, individual sounder operation and relay output
operation on Input /Output units.
Front Display
Advanced Individual test