70
Troubleshooting
Rev 12 – NOV 2019
OMMG00012
On Actuators with a
Positioner, Check status of
LED
Valve will not drive in
either direction
Check power supply
Check actuator motor
running
If motor running, replace
shear pin between valve and
actuator
If not running, ensure local
power supply is compatible
with nameplate voltage and
current rating.
Check if motor overheated
Refer to “Motor overheating”
below
Check motor run capacitor
Replace capacitor
Check Positioner
Replace Positioner
Valve operates slowly
Check mains voltage
matches rating plate
Incomplete travel
Check limit switch setting
Adjust
Check for obstructions in
valve
Clear obstructions
Check mechanical stops on
actuator
Adjust
Check setting of
Potentiometer (4.8.7, page
Adjust position feedback
sensor
Check 4-20mA input
resistance (terminals 16 &
17)
If not 200 ohms, use
Configurator to check
incoming demand data
(OMM47962X00013).
Check data output from
Configurator on PC
If 2
nd
column % does not
match 4-20mA input, replace
Positioner
Motor overheating
Check if valve is oscillating
See “Valve is oscillating”
above
Check for obstructions in
valve
Clear obstructions
Check ambient temperature
Reduce ambient temperature
Ensure local power supply is
compatible with nameplate
voltage and current rating.
Check electrical connections
Moisture/Condensation Check heater in actuator
connected
Connect heater
Summary of Contents for 10GEF
Page 2: ......
Page 14: ...14 System Overview Rev 12 NOV 2019 OMMG00012...
Page 52: ...52 Electric Actuator Rev 12 NOV 2019 OMMG00012...
Page 54: ...54 PID Controller Rev 12 NOV 2019 OMMG00012...
Page 64: ...64 System Integration Rev 12 NOV 2019 OMMG00012 Fig 22 System Wiring Diagram 8072D Controller...
Page 67: ...67 System Integration OMMG00012 Rev 12 NOV 2019...
Page 68: ...68 System Integration Rev 12 NOV 2019 OMMG00012...
Page 74: ...74 Technical Data Rev 12 NOV 2019 OMMG00012 9 1 1 Valve Bore Fig 25 Valve Selection Curve...