34
Electric Actuator
Rev 12 – NOV 2019
OMMG00012
4.6
Positioner Configuration and Calibration
The Positioner is provided fully calibrated and configured according to the
model code of the valve that the actuator is fitted to. Changes can be made if
required by means of a Configurator box connected between the positioner and
the actuator to access calibration and configuration options. The following
parameters can be accessed:
The options within each parameter are:
•
CW / ACW on increasing mA
o
CW on increasing mA
o
ACW on increasing mA
•
Action on loss of mA demand signal
o
Move to 4mA position
o
Move to 20mA position
o
No actuator movement (default)
•
Initiate actuator calibration
o
Start actuator calibration
•
Deadband
o
1% to 9% in 1% steps
•
4-20mA output
o
Output equals current position
o
Output equals demand input
o
Output is scaled position error, 4mA is no position error
o
Output is scaled position error, 12mA is no position error
4.6.1
Configurator
Refer to OMM47962X00013 for details of how to use the 47962X Configurator
to access and change the above parameters.
Summary of Contents for 10GEF
Page 2: ......
Page 14: ...14 System Overview Rev 12 NOV 2019 OMMG00012...
Page 52: ...52 Electric Actuator Rev 12 NOV 2019 OMMG00012...
Page 54: ...54 PID Controller Rev 12 NOV 2019 OMMG00012...
Page 64: ...64 System Integration Rev 12 NOV 2019 OMMG00012 Fig 22 System Wiring Diagram 8072D Controller...
Page 67: ...67 System Integration OMMG00012 Rev 12 NOV 2019...
Page 68: ...68 System Integration Rev 12 NOV 2019 OMMG00012...
Page 74: ...74 Technical Data Rev 12 NOV 2019 OMMG00012 9 1 1 Valve Bore Fig 25 Valve Selection Curve...